| Plan Review Notes For Permit 06061179 |
| Permit Number |
06061179 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-10-19 20:05:53 | ***REDLINED THIRD TIME THE REQUIREMENTS OF 700.12E. | | | | | | "THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE | | | THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL | | | LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL | | | SWITCHES." |
|