| Plan Review Notes For Permit 06061149 |
| Permit Number |
06061149 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-06-25 00:00:00 | *** UNSAT *** | | | | | | | | | 1) NOTE: PLEASE SUBMIT AN ELECTRICAL | | | RISER DIAGRAM WITH THE NEW PROPOSED | | | WORK. | | | PLEASE INCLUDE SEC'S, CONDUITS ETC. | | | PLEASE INCLUDE NEW GROUNDING ELECTRODE | | | SYSTEM. | | | PLEASE INCLUDE AIC RATING FOR NEW | | | SERVICE EQUIPMENT. | | | PLEASE INDICATE SIZE OF NEW M/M, AND | | | LOAD ON EXISTING. | | | PLEASE SHOW HOW FEEDS TO EXISTING | | | CIRCUITS WILL TAKE PLACE. | | | 215.5,110.9,240.4,310.16, 250.50, ETC | | | | | | 2) NOTE: PLEASE BE SURE ALL PLANS | | | CONTAIN THE PRINTED ANME AND SIGNATURE | | | OF THE PERSONRESPONSIBLE FOR | | | PLANS/DESIGN. | | | FBC 106.1.2 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|