| 2006-06-29 00:00:00 | ******DENIED****** |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR PLAN REVIEW FOR A GAS PERMIT: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, AND ALL PIPE SIZES. |
| | 3. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4).(NOTE: THE |
| | LONGEST RUN INDICATED ON DRAWING IS |
| | INCORRECT, AND THE PIPE SIZING IS WRONG |
| | PER FBC-2004 FUEL GAS TABLES 402.4(2), |
| | AND 402.4(20). SYSTEM MIGHT NEED TO GO |
| | TO A 2LB SYSTEM WITH REGULATORS, PLEASE |
| | CORRECT FOR RESUBMITTAL) |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| | RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. PLEASE SEE MARKED UP DRAWING IN |
| | RED INK, AND ATTACHED SIZING TABLESFOR |
| | REFERENCE FOR RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |