| | DENIED |
| | |
| | 1)THE GLASS BLOCK MEETS THE DESIGN PRESSURES REQUIRED |
| | BUT IS ONLY SMALL MISSILE IMPACT RATED. PER 1609.1.4 |
| | FBC GLAZING WITHIN THE FIRST 30 FEET FROM GRADE ARE |
| | REQUIRED TO MEET LARGE MISSILE IMPACT TEST REQUIREMENTS |
| | THEREFORE THESE OPENINGS WILL REQUIRE AN IMPACT |
| | PROTECTION SYSTEM. IF THIS PRODUCT IS USED SHUTTERS |
| | WILL BE REQUIRED. PITTSBURGH CORNING HAS A GLASS BLOCK |
| | SYSTEM THAT USES SILICONE RATHER THAN MORTAR THAT MEETS |
| | THE REQUIREMENTS OF SMALL AND LARGE MISSILE IMPACT |
| | RATING. |
| | |
| | 2)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA |
| | STATE PRODUCT APPROVAL SHEETS WHEN AVAILABLE. THEY CAN |
| | BE SEARCHED FOR ON WWW.FLORIDABUILDING.ORG.WHEN |
| | AVAILABLE AND NOT SUBMITTED APPLICATIONS WILL BE |
| | DENIED.*******PLEASE SEE THE FL# WRITTEN AT TOP OF |
| | MIAMI-DADE NOA, IF SILICONE SYSTEM IS USED FL # IS |
| | 5357-R1******** |
| | |
| | 3)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE |
| | 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC* |
| | |
| | 4)ORIGINAL DRAWINGS DO NOT SHOW GLASS BLOCK, REVISED |
| | SHEET SHOWING LOCATION OF NEW GLASS BLOCK OPENING ARE |
| | REQUIRED WITH THE PRODUCT APPROVAL. |
| | |
| | 5)THIS IS A REVISION TO THE PERMITTED SET OF DRAWING |
| | NOT A SUBMITTAL AND AS SUCH REQUIRES A REVISION FEE. |
| | |