Plan Review Notes
Plan Review Notes For Permit 06061101
Permit Number 06061101
Review Stop B
Sequence Number 4
Notes
Date Text
2007-04-06 15:09:26 
 DENIED
  
 1)PER 713.13(2) F.S.
 IF THE IMPROVEMENT DESCRIBED IN THE NOC HAS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING THE NOTICE IS
 VOID. ****PLEASE SUBMIT A RERECORDED NOC.****
  
 2)SUBMIT ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR
 BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD
 ****2 COMPLETE COPIES THAT ARE SIGNED AND SEALED BY THE
 TRUSS MANUFACTURERS ENGINEER ARE REQUIRED.****
  
 3)SUBMIT ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL. ****ONLY ONE COPY WAS SUBMITTED AND IT
 WAS NOT DATED.****
  
 4)THE FOLLOWING CORRECTIONS ARE REQUIRED FOR THE
 PRODUCT APPROVALS
  
 A) CHOOSE THE TYPE OF GAF SHINGLE THAT WILL BE USED
 FROM THE FLORIDA PAGE AND SUBMIT WITH THE CORRECT NOA
 B) CHOOSE THE TYPE OF WINDOW THAT YOU WILL USE FROM THE
 FLORIDA PAGES AND SUBMIT WITH THE ACCOMPANYING NOA C)
 TWO DIFFERENT PRODUCT APPROVALS WERE SUBMITTED FOR
 STORM PANELS PLEASE SUBMIT 2 COPIES OF THE PRODUCT YOU
 WILL BE USING.
 D) THE DOOR MANUFACTURER THAT WAS SUBMITTED DOES NOT
 CARRY ANY APPROVED STATUS IN THE 2004 FLORIDA SYSTEM OR
 ON THE MIAMI-DADE SITE. PLEASE SUBMIT 2 COPIES OF AN
 APPROVED DOOR.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716