| 2006-09-19 00:00:00 | ********** UNSAT 3RD REVIEW ********* |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| | TWO REVIEWS ARE STILL IN NEED OF |
| | ADDRESSING. |
| | |
| | 1) NOTE: PLEASE SEE DEDICATED BATH(S) RM |
| | CIRCUIT(S) ARE STILL BEING SHOWN A 220V |
| | ON 2-POLE BREAKERS. |
| | 210.52D,210.11C3 |
| | BOTH PREVIOUS REVIEWS |
| | |
| | 2) NOTE: PLEASE SEE THE SMALL APPLIACNE |
| | CIRCUIT IS BEING SHOWN ON A 220V -2-POLE |
| | BRKR? |
| | |
| | 3) NOTE: PLEASE SEE ARC FAULT PROTECTION |
| | IS STILL BEING SHOWN FOR RECEPTS ONLY AS |
| | NOTED FROM THE 1999 NEC. BOTH PREVIOUS |
| | REVIEWS. |
| | PLEASE SEE 210.12 2002 NEC> |
| | |
| | 4) NOTE: PLEASE SEE ONLY SET OFNEW |
| | PLANS ARE BEING SUBMITTED. |
| | PLEASE SEE ONLY ONE NEW AND ONE OLD WAS |
| | SUBMITTED. |
| | PLEASE SEE FBC ADMIN SECT 106.1 AS 2 MIN |
| | ARE REQUIRED ALONG WITH ONE SET OF THE |
| | OLD/VOIDED PLANS. |
| | |
| | 5) NOTE: PLEASE SEE PREVIOUS NOTE WHICH |
| | MENTIONED FS 553.80(2)(B) WITH RESPECT |
| | TO REPEAT COMMENTS FOR CODE COMPLIANCE. |
| | PLEASE KNOW, A 4X FEE HAS NOW BEEN ADDED |
| | FOR REPEAT COMMENTS. THE FEE FO $960.00 |
| | IS NOW DUE BEFORE RESUBMITTING PLANS. |
| | PLEASE ALSO KNOW THAT THE 2ND RESUB FEE |
| | WAS NOT PAID WHEN PLANS WERE RESUBMITTED |
| | FOR THIS REVIEW AND WAS NOW BEEN ADDED |
| | AND IS ALSO OWED BEFORE RESUBMITTING |
| | PLANS. |
| | PLEASE SEE FS 553.80(2)(B), AS THIS |
| | WOULD BE REQUIRED FOR EACH TIME IF PLANS |
| | FAIL FOR ANY REPEAT COMMENTS. |
| | |
| | ** NEW NOTES ** |
| | |
| | 6) NOTE: PLEASE SE PANEL SCHEDULE SHOWS |
| | 50A OCP FOR THE 10KW HEAT ON AHU. PLEASE |
| | VERIFY AS THE CODE IN 424.3B REQUIRES A |
| | MIN OF 125% FOR OCP. |
| | |
| | 7) NOTE: PLEASE SEE PANEL SCHEDULE SHOWS |
| | A DEDICATE CIRCUIT FOR OVERHEAD GARAGE |
| | DOOR, HOWEVER NO GARAGE OR OVERHEAD DOOR |
| | IS SHOWN ON PLANS??? |
| | PLEASE VERIFY |
| | 106.1.2 |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |