2006-08-14 00:00:00******DENIED 2ND TIME******
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. THE FOLLOWING INFORMATION IS STILL
 REQUIRED BY PLUMBING PLAN REVIEW DUE TO
 THE FACT THAT THE SAME PLANWAS
 RESUBMITTED WITH NO CORRECTIONS.
 2. ONLY ONE PLAN WAS AGAIN RESUBMITTED,
 NOTE: PER FBC-2004 CHAPTER 1, SECTION
 106.1, TWO (2) SETS OF PLANS REQUIRED.
 3. PLEASE SEE ATTACHED FLORIDA STATUTE
 533.80(2)(B) IN RESPECT WITH REPEAT
 COMMENTS FOR CODE COMPLIANCE.
 **BELOW ARE REPEAT COMMENTS FROM 1ST
 REVIEW**
 4.PER FBC-2004 SEC, 708.3.4 BASE OF
 STACK: A CLEANOUT SHALL BE PROVIDED AT
 THE BASE OF EACH WASTE OR SOIL STACK.
 5. PER FBC-2004 TABLE 906.1: THE MAXIMUM
 DISTANCE OF A 2" TRAP WITH A 2" FIXTURE
 DRAIN IS 6', A RELIEF VENT IS REQUIRED.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: PLEASE SEE CORRECTED
 ISOMETRIC SANITARY RISER DIAGRAM ON
 SHEET 2 OF 4 IN RED INK FOR RE REFERENCE
 FOR RESUBMITTAL. ONLY ONE CORRECTED
 DRAWING IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  