| 2006-08-14 00:00:00 | |
| | |
| | DENIED |
| | |
| | THE FOLLOWING PLAN REVIEW COMMENTS WERE |
| | NOT ADDRESSED |
| | |
| | 1) BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SETS OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561) 233-5025 FOR MORE |
| | INFORMATION. PLEASE MAKE CORRECTIONS TO |
| | DRAWINGS BEFORE SUBMITTING TO COUNTY FOR |
| | IMPACT FEES & STAMP |
| | |
| | 2) THE STATE OF FLORIDA REQUIRES |
| | COLLECTION OF A RADON SURCHARGE ON ALL |
| | NEW CONSTRUCTION COMPUTED ON UNDER ROOF |
| | FLOOR SPACE PER 10D-91 FAC. THESE FEES |
| | WILL BE ADDED TO THE PERMIT APPLICATION |
| | FEES |
| | |
| | 3) PROVIDE 2 COPIES OF SURVEY |
| | |
| | 4) PROVIDE 2 OR MORE SETS OF |
| | CONSTRUCTION DOCUMENTS WITH PERMIT |
| | APPLICATION PER 106.1 (2 COPIES OF |
| | DRAWINGS AND PRODUCT APPROVALS) |
| | |
| | 5) THE PERMIT APPLICATION SHALL INCLUDE |
| | TWO COPIES OF EACH PRODUCT APPROVAL THAT |
| | IS RELEVANT PER 9B-72. THESE SHOULD |
| | INCLUDE THE FLORIDA STATE APPROVAL COVER |
| | PAGES, AND THE PRODUCT NOA THAT LISTS |
| | THE SYSTEM COMPONENTS/ FASTENER LIST |
| | PAGES, THE PAGES WITH THE CHOSEN |
| | ASSEMBLY/ SYSTEM TO BE USED AND THE |
| | GENERAL LIMITATIONS PAGE. ALL CAN BE |
| | FOUND ON WWW.FLORIDABUILDING.ORG |
| | (PRODUCT APPROVALS REQUIRED FOR ROOFING, |
| | WINDOW, DOOR) |
| | |
| | 6) THOSE PRODUCTS WHICH ARE REGULATED BY |
| | DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL PER 106.3.3 FBC* |
| | |
| | 7) SUBMIT ENGINEERED TRUSS DRAWINGS THAT |
| | COMPLY WITH R802.10.1 FBC WITH PERMIT |
| | APPLICATION OR BEFORE INSTALLATION |
| | |
| | 8) DESIGN PARAMATER LETTER HAS WHITE |
| | OUT, THIS IS NOT ACCEPTABLE. PLEASE |
| | REPRINT WITH CORRECTIONS AND SUBMIT 2 |
| | COPIES (ONE WITH EACH SET OF DRAWINGS) |
| | OR ADD TO NEW DRAWINGS |
| | |
| | 9) SUBMIT ENERGY CALC'S PER 13-101.2.2 |
| | FBC. BE SURE THAT THEY ARE SIGNED AND |
| | DATED BY PREPARER AND OWNER/AGENT PRIOR |
| | TO SUBMITTAL. NOTE THAT THERE ARE NO |
| | MECHANICAL DRAWINGS SUBMITTED |
| | |
| | 10) DRAWINGS DO NOT ADEQUATELY SHOW THE |
| | FOLLOWING, WINDOW SILL DETAIL, CEILING |
| | INSULATION VALUE, MEAN ROOF HEIGHT, TOP |
| | OF BEAM ELEVATION, FIN. FLOOR ELEVATION |
| | |
| | 11) PROVIDE ATTIC ACCESS ON DRAWINGS |
| | PER R807.1 |
| | |
| | |
| | BLDG PLAN REVIEW |
| | ADRIAN MORSE |
| | 561-805-6716 |
| | |
| | |
| | |
| | |
| | |