Plan Review Notes
Plan Review Notes For Permit 06061101
Permit Number 06061101
Review Stop B
Sequence Number 2
Notes
Date Text
2006-08-14 00:00:00 
  
 DENIED
  
 THE FOLLOWING PLAN REVIEW COMMENTS WERE
 NOT ADDRESSED
  
 1) BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION. PLEASE MAKE CORRECTIONS TO
 DRAWINGS BEFORE SUBMITTING TO COUNTY FOR
 IMPACT FEES & STAMP
  
 2) THE STATE OF FLORIDA REQUIRES
 COLLECTION OF A RADON SURCHARGE ON ALL
 NEW CONSTRUCTION COMPUTED ON UNDER ROOF
 FLOOR SPACE PER 10D-91 FAC. THESE FEES
 WILL BE ADDED TO THE PERMIT APPLICATION
 FEES
  
 3) PROVIDE 2 COPIES OF SURVEY
  
 4) PROVIDE 2 OR MORE SETS OF
 CONSTRUCTION DOCUMENTS WITH PERMIT
 APPLICATION PER 106.1 (2 COPIES OF
 DRAWINGS AND PRODUCT APPROVALS)
  
 5) THE PERMIT APPLICATION SHALL INCLUDE
 TWO COPIES OF EACH PRODUCT APPROVAL THAT
 IS RELEVANT PER 9B-72. THESE SHOULD
 INCLUDE THE FLORIDA STATE APPROVAL COVER
 PAGES, AND THE PRODUCT NOA THAT LISTS
 THE SYSTEM COMPONENTS/ FASTENER LIST
 PAGES, THE PAGES WITH THE CHOSEN
 ASSEMBLY/ SYSTEM TO BE USED AND THE
 GENERAL LIMITATIONS PAGE. ALL CAN BE
 FOUND ON WWW.FLORIDABUILDING.ORG
 (PRODUCT APPROVALS REQUIRED FOR ROOFING,
 WINDOW, DOOR)
  
 6) THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 7) SUBMIT ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT
 APPLICATION OR BEFORE INSTALLATION
  
 8) DESIGN PARAMATER LETTER HAS WHITE
 OUT, THIS IS NOT ACCEPTABLE. PLEASE
 REPRINT WITH CORRECTIONS AND SUBMIT 2
 COPIES (ONE WITH EACH SET OF DRAWINGS)
 OR ADD TO NEW DRAWINGS
  
 9) SUBMIT ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL. NOTE THAT THERE ARE NO
 MECHANICAL DRAWINGS SUBMITTED
  
 10) DRAWINGS DO NOT ADEQUATELY SHOW THE
 FOLLOWING, WINDOW SILL DETAIL, CEILING
 INSULATION VALUE, MEAN ROOF HEIGHT, TOP
 OF BEAM ELEVATION, FIN. FLOOR ELEVATION
  
 11) PROVIDE ATTIC ACCESS ON DRAWINGS
 PER R807.1
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  