2006-07-03 00:00:00******DENIED******
 REFERENCE: FBC-2004 PLUMBING
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLUMBING PLAN REVIEW:
  
 1. PER FBC-2004 SEC. 708.3.4 BASE OF
 STACK: A CLEANOUT SHALL BE PROVIDED AT
 THE BASE OF EACH WASTE OR SOIL STACK.
 2. PER FBC-2004 TABLE 906.1: THE MAXIMUM
 DISTANCE OF A 2" TRAP WITH A 2" FIXTURE
 DRAIN IS 6', A RELIEF VENT IS REQUIRED.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. PLEASE SEE CORRECTED ISOMETRIC
 SANITARY RISER DIAGRAM ON SHEET 2 OF 4
 IN RED INK FOR RFEERENCE FOR
 RESUBMITTAL.
  