| Plan Review Notes For Permit 06061101 |
| Permit Number |
06061101 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-07-03 00:00:00 | ******DENIED****** | | | REFERENCE: FBC-2004 PLUMBING | | | | | | THE FOLLOWING INFORMATION IS REQUIRED | | | FOR PLUMBING PLAN REVIEW: | | | | | | 1. PER FBC-2004 SEC. 708.3.4 BASE OF | | | STACK: A CLEANOUT SHALL BE PROVIDED AT | | | THE BASE OF EACH WASTE OR SOIL STACK. | | | 2. PER FBC-2004 TABLE 906.1: THE MAXIMUM | | | DISTANCE OF A 2" TRAP WITH A 2" FIXTURE | | | DRAIN IS 6', A RELIEF VENT IS REQUIRED. | | | | | | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN | | | RESUBMITTING, PLEASE REPLACE ONLY SHEETS | | | WHICH HAVE CHANGED, AND PROVIDE ONE COPY | | | OF ALL OLD/VOIDED SHEETS FOR REFERENCE | | | ONLY. PLEASE SEE CORRECTED ISOMETRIC | | | SANITARY RISER DIAGRAM ON SHEET 2 OF 4 | | | IN RED INK FOR RFEERENCE FOR | | | RESUBMITTAL. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 | | | | | | | | | | | | | | | |
|