| 2006-06-28 00:00:00 | ******* UNSAT ********* |
| | |
| | 1) NOTE: PELASE SEE MISSIGN EGRESS LT |
| | AND CONTROL AST REAR OF ADDTION. 210.70, |
| | LS101 7.8 |
| | |
| | 2) NOTE: PLEASE SEE BATH RM GFI RECEPT |
| | SHALL BE WITHIN 3' OF THE EDGE OF THE |
| | SINK, WITHOUT CROSSING OVER THE OTHER |
| | SINK. THIS SHALL BE DONE BY MOVING THE |
| | GFI OR ADDING ONE. |
| | 210.52D |
| | |
| | 3) NOTE: PLEASE SEE THE DEDICATED BATH |
| | CIRCUIT IS SHOWN AS 220V/2-POLE??? |
| | PLEASE SEE 210.11C3 |
| | |
| | 4) NOTE: PLEASE SEE 250.52,210.70 AS AN |
| | ENTIRE RECEPT IS BEING SHOWN AS SWITCHED |
| | IN BEDRM WHICH IS OK, HOWEVER AN |
| | ADDITIONAL RECEPT WOULD BE REQUIRED TO |
| | MEET 210.52 |
| | IF THIS IS A 1/2 SW DEVICE, PLEASE |
| | CHANGE. |
| | |
| | 5) NOTE: PLEASE SEE ONLY ONE SM APPL |
| | CIRCUIT IS SHOWN, HOWEVER 3KW LOAD IS |
| | BEING SHOWN ONTHIS ONE CIR. |
| | PLEASE SEE 210.52B1,220.16,220.11C1 |
| | |
| | 6) NOTE: PLEASE SEE 210.8A AS THE RECEPT |
| | LOCATED OUTSIDE REQUIRED BYE 210.52E, |
| | SHOULD BE GFI. |
| | |
| | 7) NOTE: PLEASE INDICATE AND SHOW THE |
| | LAYOUT OF THE REST OF THE DWELLING AS |
| | SD'S ARE REQ'D INSIDE AND OUTSIDE ALL |
| | EXISTING SLEEPING RMS. |
| | R313, NFPA-72 11.5.1.1,11.8.3 |
| | |
| | 8) NOTE: PLEASE SEE PLANS INDICATE THE |
| | REQ'D ARC FAULT FOR DEVICES FROM THE |
| | 1999 NEC. PLEASE SEE 210.12B 2002, AS |
| | ARC FAULT PROTECTION IS REQ'D FOR ALL |
| | NEW OUTLETS IN BEDRMS. |
| | PLEASE INDICATE THIS ON PANEL SCHEDULE, |
| | NOT IN A NOTE. |
| | 408.4 |
| | |
| | 9) NOTE: PLEASE INDICATE THE NEW CIRCUIT |
| | ON PANEL SCHEDULE. 408.4. |
| | THIS IS THE SAME PANEL SCHEDULE WHICH IS |
| | BEING SUBMITTED FOR EVERY HOUSE BY THIS |
| | DRAFTMANS/DESIGNER AND EACH HOUSE SHALL |
| | BE SPECIFIC TO THAT DWELLING. |
| | PLEASE REVISE. |
| | |
| | |
| | ** IMPORTANT** |
| | PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. ONLY ONE COPY OF |
| | THE OLD/VOIDED REMOVED SHEETS SHOULD BE |
| | SUBMITTED WITH NEW SETS. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| 2006-06-27 00:00:00 | PLANS IN ELEC FOR REVIEW, WILL PROCEED |
| | INTO "F" STATUES, REVIEW TO CONTINUE ON |
| | 6/28 |