Plan Review Notes
Plan Review Notes For Permit 06061101
Permit Number 06061101
Review Stop E
Sequence Number 1
Notes
Date Text
2006-06-28 00:00:00******* UNSAT *********
  
 1) NOTE: PELASE SEE MISSIGN EGRESS LT
 AND CONTROL AST REAR OF ADDTION. 210.70,
 LS101 7.8
  
 2) NOTE: PLEASE SEE BATH RM GFI RECEPT
 SHALL BE WITHIN 3' OF THE EDGE OF THE
 SINK, WITHOUT CROSSING OVER THE OTHER
 SINK. THIS SHALL BE DONE BY MOVING THE
 GFI OR ADDING ONE.
 210.52D
  
 3) NOTE: PLEASE SEE THE DEDICATED BATH
 CIRCUIT IS SHOWN AS 220V/2-POLE???
 PLEASE SEE 210.11C3
  
 4) NOTE: PLEASE SEE 250.52,210.70 AS AN
 ENTIRE RECEPT IS BEING SHOWN AS SWITCHED
 IN BEDRM WHICH IS OK, HOWEVER AN
 ADDITIONAL RECEPT WOULD BE REQUIRED TO
 MEET 210.52
 IF THIS IS A 1/2 SW DEVICE, PLEASE
 CHANGE.
  
 5) NOTE: PLEASE SEE ONLY ONE SM APPL
 CIRCUIT IS SHOWN, HOWEVER 3KW LOAD IS
 BEING SHOWN ONTHIS ONE CIR.
 PLEASE SEE 210.52B1,220.16,220.11C1
  
 6) NOTE: PLEASE SEE 210.8A AS THE RECEPT
 LOCATED OUTSIDE REQUIRED BYE 210.52E,
 SHOULD BE GFI.
  
 7) NOTE: PLEASE INDICATE AND SHOW THE
 LAYOUT OF THE REST OF THE DWELLING AS
 SD'S ARE REQ'D INSIDE AND OUTSIDE ALL
 EXISTING SLEEPING RMS.
 R313, NFPA-72 11.5.1.1,11.8.3
  
 8) NOTE: PLEASE SEE PLANS INDICATE THE
 REQ'D ARC FAULT FOR DEVICES FROM THE
 1999 NEC. PLEASE SEE 210.12B 2002, AS
 ARC FAULT PROTECTION IS REQ'D FOR ALL
 NEW OUTLETS IN BEDRMS.
 PLEASE INDICATE THIS ON PANEL SCHEDULE,
 NOT IN A NOTE.
 408.4
  
 9) NOTE: PLEASE INDICATE THE NEW CIRCUIT
 ON PANEL SCHEDULE. 408.4.
 THIS IS THE SAME PANEL SCHEDULE WHICH IS
 BEING SUBMITTED FOR EVERY HOUSE BY THIS
 DRAFTMANS/DESIGNER AND EACH HOUSE SHALL
 BE SPECIFIC TO THAT DWELLING.
 PLEASE REVISE.
  
  
 ** IMPORTANT**
 PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING. ONLY ONE COPY OF
 THE OLD/VOIDED REMOVED SHEETS SHOULD BE
 SUBMITTED WITH NEW SETS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
2006-06-27 00:00:00PLANS IN ELEC FOR REVIEW, WILL PROCEED
 INTO "F" STATUES, REVIEW TO CONTINUE ON
 6/28