| 2006-09-25 00:00:00 | **** UNSAT 4TH REVIEW ****** |
| | |
| | *** PLEASE SEE NOTES FROM ALL PREVIOUS |
| | REVIEWS. |
| | |
| | PLEASE SEE MANY ITEMS STILL NEED TO BE |
| | ADDRESSED. |
| | |
| | 1) NOTE: PLEASE SEE "220.31B" FOR LOAD |
| | CALCULATIONS. |
| | |
| | 2) NOTE: PLEASE SEE PLANS ARE STILL |
| | MISSING OCP FOR SYSTEM BEING INSTALLED |
| | AT PANEL AND CU. |
| | PLEASE SEE 424.3B. PLEASE SEE OCP AT CU |
| | SHOULD BE SHOWN FOR UNIT AS THE OCP FOR |
| | AHU WILL NOT BE THE SAME. |
| | |
| | 3) NOTE: PLEASE SEE NOW THE CONDUCTORS |
| | HAVE BEEN INCREASED TO #6'S, HOWEVER |
| | PLEASE CLARIFY 3-#6'S & 2-#12'S TO CU. |
| | IS THE EQUIPMENT GROUNDING CONDUCTOR |
| | GOING TO BE A #6 ALSO? PLEASE SEE PIPE |
| | FILL IN TABLE OF CHAPTER 9. THIS WOULD |
| | DEPEND ON CONDUIT TYOE, HOWEVER THIS IS |
| | BEING FIGURED AT WORST CASE. PLEASE ALSO |
| | SEE 250.122 FOR MIN REQUIRED FOR THE |
| | "EQUIPMENT GROUNDIGN CONDUCTOR, THEN THE |
| | 3/4" COUNDUIT NO MATTER WHAT TYPE WOULD |
| | BE OK. PLEASE SEE NO CONDUCTORS ARE |
| | BEING SHOWN BASED ON THE OCP AT THE CU |
| | DISCONNECT TO THE CU. |
| | 240.4,310.16 ETC. |
| | |
| | 4) NOTE: PLEASE CLARIFY DISCONNECT FOR |
| | AHU? 440.11,110.26 ETC. |
| | |
| | 5) NOTE: PLEASE SEE ALL PLANS/SHEETS |
| | MUST CONTAIN THE PRINTED NAME AND |
| | SIGNATURE OF THE PERSON RESPONSIBLE FOR |
| | PLANS/DESIGNS. (INCLUDING LOAD CALCS). |
| | FBC 106.1.2. |
| | |
| | 6) NOTE: PLEASE SEE THE PREVIOUS REVIEW |
| | STATED TO SEE FS 553.80(2)(B) WITH |
| | RESPECT TO THE SAME REPEAT CODE |
| | COMPLIANT COMMENTS FOR PLANS REVIEW AS A |
| | NOTICE. |
| | PLEASE KNOW AS REQUIRED PER THE FS AS |
| | MENTIONED , A 4X FEE FOR THE PLAN REVIEW |
| | PORTION OF THE BASE PERMIT FEE HAS NOW |
| | BEEN ASSESSED AND MUST BE PAID BEFORE |
| | RESUBMITTING PLANS FOR THE 5TH REVIEW. |
| | PLEASE SEE THE FEE OF $264.33 IS NOW |
| | DUE. |
| | |
| | I HAVE CIRCILED AND REDLINED MOST |
| | LOCATIONS ON PLANS. |
| | ONCE AGAIN , IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |