2006-06-29 00:00:00******DENIED******
 REFERENCE: FBC-2004 SEC. 424.2 SWIMMING
 POOLS:
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLUMBING PLAN REVIEW FOR A POOL
 PERMIT:
  
 1. PLEASE CORRELATE THE EQUIPMENT LAYOUT
 WITH THE LEGEND ON THE 1 HP REC. PUMP W/
 APPR. HAIR & LINT STRAINER. EQUIPMENT
 LAYOUT INDICATES "B" AND THE LEGEND
 INDICATES "A". PLEASE SEE RED INK
 CIRCLES FOR REFERENCE FOR RESUBMITTAL.
 2. FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (MANUFACTURE
 SHEETS REQUIRED, PLEASE SUBMIT)
 3. FBC-2004 SEC. 424.2.14.2, OR
 FBCR-2004 SEC. R4101.14.2 WATER
 RETENTION, PROVIDE A POSITIVE MEANS OF
 RETAINING WATER IN THE HEATER WHEN PUMP
 IS SHUT OFF.(MANUFACTURE SHEETS
 REQUIRED, PLEASE SUBMIT)
 4. NOTE: THERE IS NOT A PLUMBING PERMIT
 NUMBER ASSIGNED TO POOL PERMIT
 APPLICATION, WHICH WILL MAKE IT HARD TO
 SCHEDULE POOL PLUMBING INSPECTIONS.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  