| Notes |
| Date |
Text |
| 2006-08-01 00:00:00 | FOR PLAN REVIEW AND NOT FOR PERMIT. | | | *** DENIED *** | | | 1) SEE ELECTRICAL REVIEW NOTES 1-4, | | | PLEASE CORRECT. | | | | | | 2) SEE BATHROOM EXHAUST FANS ARE | | | REMOVING 250 CFM'S FROM EACH BATHROOM, | | | SUPPLY AIR TO EACH BATHROOM IS ONLY | | | 125-150 CFM'S THIS WILL PUT THE | | | BATHROOMS AT A HIGH NEGATIVE PRESSURE, | | | ONLY 50 CFM'S EXHAUST PER BATHROOM IS | | | REQUIRED. | | | | | | 3) SEE EMPLOYEE LOUNGE EXHAUST FAN | | | REMOVING 514 CFM'S, SUPPLY AIR TO ROOM | | | IS ONLY 550 CFM'S, IS THIS WHAT YOU WANT | | | TO ACCOMPLISH. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|