Plan Review Notes
Plan Review Notes For Permit 06061050
Permit Number 06061050
Review Stop E
Sequence Number 1
Notes
Date Text
2006-07-02 00:00:00*********UNSAT ********
  
 ** PLEASE KNOW, PLANS HAVE ONLY BEEN
 SUBMITTED FOR "PLAN REVIEW" ONLY AND HAS
 NOT BEEN SUBMITTED FOR PERMIT
 APPLICATION AT THIS TIME.
  
 1) NOTE: PLEASE BE SURE PLANS REFLECT
 THE CURRENT CODES IN EFFECT. PLEASE SEE
 ELECTRICAL PLANS MENTIONS THE "LATEST
 CODES', HOWEVER PLEASE KNOW THE "LATEST
 CODES" 2005 NFPA-70 HAS NOT YET BEEN
 ADOPTEDBY THE STATE OF FLORIDA.
 PLEASE BE SURE ELECTRICAL PLANS LIST THE
 FOLLOWING AT A MIN.
 NFPA-72 2002, NFPA-72 2002, NFPA-101
 2003
 ** PLEASE ALSO SEE COVE SHEETS "T1"
 WHICH MENTIONS THE 2001 FBCFOR
 EXISTING BUILDINS? PLEASE SEE BUILDING
 REVIEW COMMENTS AS THIS SHOULD ALSO BE
 THE 2004 FBC EXISTING BUILDINGS.
 MAY NOT USE SECTIONS FROM DIFFERENT
 CODES.
  
 2) NOTE: PLEASE SEE ENGERGY CALCULATIONS
 SEEMED TO BE SIGNED BY THE SAME
 INDIVIDUAL.
 PLEASE PROVIDE SIGNED, DATED AND SEALED
 NOTORIZED LETTERS FOR THE LEGAL
 SIGNATURES OF EACH ENGINEERS.
 PLEASE KNOW, UNDER FLORIDA STATUES
 471.025, AND FLORIDA ADMINISTRATIVE CODE
 61G15-23.002 NO OTHER INDIVIDUAL MAY
 SIGN AND SEAL DOCUMNETS FOR SOMEONE
 ELSE.
 TWO OF THE SETS ENERGY CALCULATIONS OF
 THE THREE SUBMITTED SETS HAVE BEEN
 RETAINED BY THIS OFFICE. THESE SHALL BE
 RETAINED IN A FILE FOR POSSIBLE REVIEW
 BY THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEER'S AND STATE'S LEGAL COUNSEL TO
 THE BOARD.
  
 3) NOTE: PLEASE SEE "E" SHEETS ARE NOT
 SIGNED, SEALED.PLEASE SEE INFACT THE
 SHEETS CONTAIN AN "X" OVER A MARK OF
 SOME KIND.
 PLEASE SEE ALL SETS SHALL BE SIGNED,
 DATED AND SEALED BY THE SAID DESIGN
 PROFESSIONAL. FS471.025, FAC
 61G15-23.002
  
 4) NOTE: PLEASE SEE MISSING CERTIFICATE
 OF AUTHORIZATION NMBER FOR ARCHITECTURAL
 FIRM AS REQUIRED UNDERFAC 61G1-16.004,
 FS 481.219.
 PLEASE KNOW, THIS IS REQUIRED ON ALL
 SHEETS WHICH CONTAIN SAID TITLE BLOCK.
 THIS IS REQUIRED FOR ALL REVIEWS WHETHER
 OR NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 5) NOTE: PLEASE PROVIDE SCHEDULEING OF
 THE EN MANG SYSTEMS AND TIME OF DAY
 SCHEDULES.
 PLEASE CLARIFY MAX TIME PERMITTED ON
 MANUAL OVER RIDES. PLEASE SEE MANUAL
 "TIMER" TYPES ARE A MAX OF 4HRS AND ANY
 OCCUPANCY SENSOR TYPE OVER RIDE IS
 30MINS.
 PLEASE INDICATE THESE.
 FBC 13-415.1.ABC.1.1, .1.2, .1.3.
  
 6) NOTE: PLEASE PROVIDE MORE DETAIL FOR
 MAX WATTS PER SQ FT/ LIGHTING POWER
 DENSITIES ALLOWED PER 13-415.1.AB.1,
 13-415.2.ABC.1 USING EITHER TABLE
 415.2.C.1,415.2.B.1.
  
 7) NOTE: PELASE CLARIFY EXISTING MAIN
 LOCATION. UNABLE TO VERIFY
 ACCESSIBILITY, GROUPING ETC. AT THIS
 TIME. 230.70,230.72
  
 8) NOTE: IT IS NOTED THAT PROVISIONS FOR
 A "TEMP GENERATOR" IS BEING PROPOSED,
 HOWEVER PLEASE KNOW THE SCENERIO AS
 NOTED ON RISER IS NOT ACCEPTABLE TO THIS
 AHJ. PLEASE SEE 702.6 WHICH REQUIRES
 TRANSFER EQUIPMENT WHICH "WILL NOT"
 PERMIT THE POSSIBILITY OF THE POWER FROM
 TWO SEPARATE SOURCES AT THE SAME TIME.
 "TRANSFER EQUIPMENT SHALL BE SUITABLE
 FOR THE INTENDED USE AND DESIGNED AND
 INSTALLED SO AS TO PREVENT THE
 INADVERTENT INTERCONNECTION OF NORMAL
 AND ALTERNATE SOURCES OF SUPPLY IN ANY
 OPERATION OF THE TRANSFER EQUIPMENT."
 PLEASE ALSO KNOW, THE TERM "QUALIFIED
 PERSONNEL" CAN NOT BE USED AT THIS
 FACILITY DOES NOT CONTAIN 24HR
 "QUALIFIED PERSONNEL". 100.
 PLEASE PROVIDE A MTS, AND PLEASE PROVIDE
 ALL MANUFACTURES SPECS AND CUT SHEETS
 FOR PROPOSED MTS.
  
 9) NOTE: PLEASE SEE THE ADDRESS OF THIS
 PROJECT SHALL BE PLACED IN THE TITLE
 BLOCKS AT THIS TIME. PLEASE SEE THE
 ADDRESS OF "7817" S DIXIE HWY. IS THE
 PROJECT LOCATTION.
 FAC 61G1-16.004
 61G15-23.002
 ** THIS IS REQUIRED FOR ALL SHEETS AND
 FOR ALL TRADES WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 10) NOTE: PLEASE SEE THAT SHOW WINDOW
 RECEPTS LOCATED ABOVE WINDOWS WILL BE
 REQUIRED AT THE SPACING AS SETFORTH IN
 THE NEC. 210.62.
 PLEASE ALSO BE SURE TO ADJUST
 CALCULATIONS AS NEEDED PER 220.12A
  
 ** IMPORTANT**
  
 ONCE ALL REVIEWS ARE DONE AND BEFORE
 RESUBMITTING PLANS FOR REVIEW. PLEASE
 REMOVE ALL OLD/VOIDED SHEETS AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 PLEASE ONLY SUBMIT ONE "COPY/SET" OF THE
 OLD/VOIDED REMOVED SHEETS FOR REFERENCE.
 THIS IS REQUIRED FOR ALL TRADES.
 PLEASE KNOW, THIS WILL HELP TO
 ALLEAVIATE ANY POSSIBLE DELAYS IN THE
 PROCESSING AND REVIEW OF PLANS.
  
 PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  