Plan Review Notes
Plan Review Notes For Permit 06061050
Permit Number 06061050
Review Stop B
Sequence Number 1
Notes
Date Text
2006-08-09 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06061050
 ADD: 7817 S DIXIE HWY
 CONT: "PLAN REVIEW"
 STATEWIDE PERMITTING:
 TEL: (954)689-6405
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) PROVIDE LOCATION (ADDRESS) OF THE
 PROPOSED JOBSITE.
 61G1-16.004FL. ADMIN. CODE.PLANS
 PREPARED BY A REGISTERED ARCHITECT SHALL
 INCLUDE A TITLE BLOCK WHICH MUST:
 - STATE THE FIRM NAME, ADDRESS AND
 TELEPHONE NUMBER
 - STATE THE FIRM LICENSE NUMBER
 - STATE PROJECT NAME OR IDENTIFICATION
 - STATE DATE PREPARED
 - INCLUDE AN ORIGINAL SIGNATURE AND
 DATED SEAL
 - INCLUDE THE PRINTED NAME OF THE
 ARCHITECT SEALING THE PLANS
  
 4) 481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING
 ARCHITECTURAL SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 5) ADDITIONAL INFORMATION 106.1.2* T1
 BUILDING REQUIREMENTS TABLE 602 NOTE# 2,
 LANDLORD IS TO CONSTRUCT A NEW 4 HR
 DEMISSING PARTITION AT THE NORTH SIDE OF
 OFFICE DEPOT.
 THE PROPOSED 4HR RATED WALL IS BEING
 BUILT AS A FIRE WALL SEPERATING
 PROPERTIES, IS THIS PROPERTY BEING
 SEPERATED INTO A SEPERATE LOT? OTHERWISE
 THE NORTHWALL OF OFFICE DEPOT ONLY NEEDS
 TO MEET THE REQUIREMENTS OF 708 FIRE
 PARTITIONS ( TENANT SEPERATION).
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  