| Plan Review Notes For Permit 06061027 |
| Permit Number |
06061027 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-07-24 00:00:00 | | | | | | | DENIED | | | | | | 1) DRAWING STATES SH SINGLE HUNG TYPE | | | WINDOW AND THE PRODUCT APPROVAL IS FOR | | | AWNING TYPE EGRESS WINDOW PLEASE CLARIFY | | | | | | 2) PRODUCT APPROVAL STATES A MAXIMUM | | | SIZE OF 37" AND DRAWING SHOWS SH33 AND | | | SH34 THESE DESIGNATIONS ARE FOR 53" WIDE | | | WINDOWS. IF 2 H33 OR H34 UNITS ARE BEING | | | USED PLEASE SUBMIT PRODUCT APPROVALS FOR | | | MULLIONS | | | | | | 3) THIS HOUSE HAS A HISTORIC DESIGNATION | | | PLEASE SEE HISTORIC FOR APPROVAL BEFORE | | | RESUBMITTAL TO CONSTRUCTION SERVICES | | | | | | 4) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT IS REQUIRED PRIOR TO | | | A PERMIT BEING ISSUED | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|