Plan Review Notes
Plan Review Notes For Permit 06061005
Permit Number 06061005
Review Stop G
Sequence Number 3
Notes
Date Text
2006-09-01 00:00:00******DENIED 3RD TIME******
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS STILL
 REQUIRED FOR GAS PLAN REVIEW:
  
 1. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 2. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). NOTE: THIS INCLUDES THE
 EXISTING BTU LOAD, PLEASE INDICATE THE
 EXISTING BTU LOAD AS WELL AS THE NEW BTU
 LOAD ON THE DRAWING.
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). NOTE: THIS
 INCLUDES THE EXISTING SYSTEM AS WELL AS
 THE NEW PROPOSED SYSTEM TO THE
 GENERATOR.
 4. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 5. NOTE: PLEASE SEE A 4X FEE FOR THE
 PLAN REVIEW PORTION OF THE PERMIT FEE
 HAS NOW BEEN ASSESSED AS REQUIRED PER FS
 553.80(2)(B).
 6. NOTE: PLEASE KNOW THE GAS PERMIT
 APPLICATION WAS NOT IN THE PACKAGE.
 PLEASE BE SURE THE APPLICATION IS
 BROUGHT BACK IN.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  