Plan Review Notes
Plan Review Notes For Permit 06061005
Permit Number 06061005
Review Stop G
Sequence Number 2
Notes
Date Text
2006-08-03 00:00:00******DENIED 2ND TIME******
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS STILL
 REQUIRED FOR GAS PLAN REVIEW:(NOTE: COM-
 MENTS NOT ADDRESSED FROM PREVIOUS GAS
 PLAN REVIEW)
  
 1. PLEASE CLEARLY INDICATE ON THE
 ISOMETRIC DRAWING IF THE GALVANIZED PIPE
 IS ABOVE GROUND STRAPPED TO THE WALL.
 (NOTE) GALVANIZED PIPE UNDERGROUND IS
 UNACCEPTABLE PER FBC-2004 FUEL GAS, SEC-
 TION 404.8.
 2. TYPE OF GAS, (LP OR NATURAL) PLEASE
 INDICATE THI ON THE ISOMETRIC DRAWING.
 3. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI ON
 THE ISOMETRIC DRAWING. (NOTE: IF SYSTEM
 IS 0.5 PSI PIPING IS SIZED WRONG PER
 FBC-2004 TABLE 402.4 (2), SEE ATTACHED
 TABLE FOR REFERENCE FOR RESUBMITTAL.)
 4. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved