| Date |
Text |
| 2006-08-03 00:00:00 | ******DENIED 2ND TIME****** |
| | REFERENCE: FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | |
| | THE FOLLOWING INFORMATION IS STILL |
| | REQUIRED FOR GAS PLAN REVIEW:(NOTE: COM- |
| | MENTS NOT ADDRESSED FROM PREVIOUS GAS |
| | PLAN REVIEW) |
| | |
| | 1. PLEASE CLEARLY INDICATE ON THE |
| | ISOMETRIC DRAWING IF THE GALVANIZED PIPE |
| | IS ABOVE GROUND STRAPPED TO THE WALL. |
| | (NOTE) GALVANIZED PIPE UNDERGROUND IS |
| | UNACCEPTABLE PER FBC-2004 FUEL GAS, SEC- |
| | TION 404.8. |
| | 2. TYPE OF GAS, (LP OR NATURAL) PLEASE |
| | INDICATE THI ON THE ISOMETRIC DRAWING. |
| | 3. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI ON |
| | THE ISOMETRIC DRAWING. (NOTE: IF SYSTEM |
| | IS 0.5 PSI PIPING IS SIZED WRONG PER |
| | FBC-2004 TABLE 402.4 (2), SEE ATTACHED |
| | TABLE FOR REFERENCE FOR RESUBMITTAL.) |
| | 4. FBC-2004 CHAPTER 1,SECTION 106.3.4.2: |
| | THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| | THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| | NAME, AND ALSO DATE DRAWING. PLEASE DO |
| | THIS PRIOR TO RESUBMITTING. |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| | RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |
| | |
| | |
| | |
| | |
| | |