Plan Review Notes
Plan Review Notes For Permit 06061002
Permit Number 06061002
Review Stop E
Sequence Number 3
Notes
Date Text
2006-08-27 00:00:00******* UNSAT3RD REVIEW ********
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEWS WHICH STILL ARE IN NEED OF
 ADDRESSING.
 PLEASE SEE NEW NOTE ADDED.
  
  
 1) NOTE: OK.
  
 2) NOTE: NO, SAME NOTE>, SPEC SHOW MORE
 THAN ONE ATS.
  
 ** PREVIOUS REVIEW NOTE 2ND REVIEW **
 SAME, PLEASE BE SURE TO HIGH-
 LIGHT UNIT.
  
 ** PREVIOUS REVIEW NOTE1ST REVIEW **
 PLEASE SEE THAT THE ATS AS
 SHOWN MUST BE "SERVICE ENTRANCE RATED,
 CONTAINING A MANUAL MEANS OF DISCONNECT
 RATED FOR THE LOAD SERVED ETC
 PLEASE "HIGHLIGHT" THE ATS.
 230.70,230.76,230.79
  
 3) NOTE: NO, PLEASE SEE NO DISCONNECT IS
 BEING SHOWN AND GROUPED WITH THE NEW
 MAIN. **PLEASE SEE THAT GENERAC NOW
 MAKES A SE RATED ATS WHICH MEETS CODE
 COMPLIANCE FOR THE THE DISCONNECITNG OF
 THE FPL POWER AND THE FEEDERS FROM THE
 GEN. (RTSE WHICH CONTAINS TWO-200A
 BREAKERS) THIS IS ONLY NOTED AS THE RTSE
 IS NOT THE ONLY WAY TO MEET CODE
 COMPLIANCE FOR THE DISCONNETING OF
 FEEDERS.225.34, 230.72
 THE BREAKER INSIDE THE GEN CAN NOT BE
 USED AS IT DOES NOT MEET CODEAND THE
 ATS SUBMITTED ONLY DISCONNECTS THE POWER
 FROM FPL. THE TOGGLE SWITCH IN THIS TYPE
 OF ATS DOE NOT MEET CODE FOR DISCONNECT
 RATED FOR THE LOAD SERVED.
  
 ** PREVIOUS REVIEW NOTES 2ND REVIEW **
 SAME, PLEASE SEE NO DISCONNECT
 SHOWN.
 ** PLEASE KNOW, GENERAC NOW HAS A NEW SE
 RATED ATS ON THE MARKET WHICH WOULD MEET
 THIS AS IT CONTAINS A MANUAL MEANS OF
 DISCONNECT FOR THE NORMAL (FPL) SIDE AND
 THE EM/GEN FEEDER SIDE. THIS IS NO WAY
 SAYING THIS NEW UNIT HAS TO BE USED.
 THIS ONLY REQUIRES A DISCONNECTING MEANS
 AND DOES NOT REQUIRED OCP. CAN BE A
 KNIFE TYPE SWITCH ETC.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1 **
 PLEASE SEE MISSING DISCONNECT
 FOR FEEDERS FROM GEN GROUPED WITH NEW
 MAIN. BRKR INSIDE GEN MAY NOT SERVE AS
 THIS DISCONNECT MEANS
 225.31-225.39
  
 4) NOTE: OK.
  
 5) NOTE: OK.
  
 6) NOTE: OK.
  
 7) NOTE: OK.
  
 8) NOTE: NO.
  
 ** PREVIOUS REVIEW NOTE REVIEW #2**
 SAME, PLEASE SEE ABOVE NOTE
 WITH RESPECT TO THE ATS BEING INSTALLED.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1 **
 PLEASE INDICATE AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT.
  
 9) NOTE: OK.
  
 10) NOTE: OK.
  
 ** NEW NOTES **
  
 11) NOTE: PLEASE SEE A 4X FEE FOR THE
 PLAN REVIEW PORTION OF THE PERMIT FEE
 HAS NOW BEEN ASSESSED AS REQUIRED PER FS
 553.80(2)(B). PLEASE KNOW THE FEE OF
 $520.68 IS DUE BEFORE PLANS MAY BE
 RESUBMITED.
  
 12) NOTE: PLEASE KNOW THE PERMIT
 APPLICATION WAS NOT IN PACKAGE. PLEASE
 BE SURE THE APPLICATION IS BROUGHT BACK
 IN. PLEASE ALSO BE SURE THAT THE
 ELECTRICLA PERMIT LINE IS SIGNED SO AN
 ELECTRICAL PERMIT (GEN-ELEC) PERMIT
 NUMBER CAN BE GENERATED FOR THE
 ELECTRICALPORTION OF THE GENERATOR
 INSTALLATION.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]