| 2006-08-27 00:00:00 | ******* UNSAT3RD REVIEW ******** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEWS WHICH STILL ARE IN NEED OF |
| | ADDRESSING. |
| | PLEASE SEE NEW NOTE ADDED. |
| | |
| | |
| | 1) NOTE: OK. |
| | |
| | 2) NOTE: NO, SAME NOTE>, SPEC SHOW MORE |
| | THAN ONE ATS. |
| | |
| | ** PREVIOUS REVIEW NOTE 2ND REVIEW ** |
| | SAME, PLEASE BE SURE TO HIGH- |
| | LIGHT UNIT. |
| | |
| | ** PREVIOUS REVIEW NOTE1ST REVIEW ** |
| | PLEASE SEE THAT THE ATS AS |
| | SHOWN MUST BE "SERVICE ENTRANCE RATED, |
| | CONTAINING A MANUAL MEANS OF DISCONNECT |
| | RATED FOR THE LOAD SERVED ETC |
| | PLEASE "HIGHLIGHT" THE ATS. |
| | 230.70,230.76,230.79 |
| | |
| | 3) NOTE: NO, PLEASE SEE NO DISCONNECT IS |
| | BEING SHOWN AND GROUPED WITH THE NEW |
| | MAIN. **PLEASE SEE THAT GENERAC NOW |
| | MAKES A SE RATED ATS WHICH MEETS CODE |
| | COMPLIANCE FOR THE THE DISCONNECITNG OF |
| | THE FPL POWER AND THE FEEDERS FROM THE |
| | GEN. (RTSE WHICH CONTAINS TWO-200A |
| | BREAKERS) THIS IS ONLY NOTED AS THE RTSE |
| | IS NOT THE ONLY WAY TO MEET CODE |
| | COMPLIANCE FOR THE DISCONNETING OF |
| | FEEDERS.225.34, 230.72 |
| | THE BREAKER INSIDE THE GEN CAN NOT BE |
| | USED AS IT DOES NOT MEET CODEAND THE |
| | ATS SUBMITTED ONLY DISCONNECTS THE POWER |
| | FROM FPL. THE TOGGLE SWITCH IN THIS TYPE |
| | OF ATS DOE NOT MEET CODE FOR DISCONNECT |
| | RATED FOR THE LOAD SERVED. |
| | |
| | ** PREVIOUS REVIEW NOTES 2ND REVIEW ** |
| | SAME, PLEASE SEE NO DISCONNECT |
| | SHOWN. |
| | ** PLEASE KNOW, GENERAC NOW HAS A NEW SE |
| | RATED ATS ON THE MARKET WHICH WOULD MEET |
| | THIS AS IT CONTAINS A MANUAL MEANS OF |
| | DISCONNECT FOR THE NORMAL (FPL) SIDE AND |
| | THE EM/GEN FEEDER SIDE. THIS IS NO WAY |
| | SAYING THIS NEW UNIT HAS TO BE USED. |
| | THIS ONLY REQUIRES A DISCONNECTING MEANS |
| | AND DOES NOT REQUIRED OCP. CAN BE A |
| | KNIFE TYPE SWITCH ETC. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #1 ** |
| | PLEASE SEE MISSING DISCONNECT |
| | FOR FEEDERS FROM GEN GROUPED WITH NEW |
| | MAIN. BRKR INSIDE GEN MAY NOT SERVE AS |
| | THIS DISCONNECT MEANS |
| | 225.31-225.39 |
| | |
| | 4) NOTE: OK. |
| | |
| | 5) NOTE: OK. |
| | |
| | 6) NOTE: OK. |
| | |
| | 7) NOTE: OK. |
| | |
| | 8) NOTE: NO. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #2** |
| | SAME, PLEASE SEE ABOVE NOTE |
| | WITH RESPECT TO THE ATS BEING INSTALLED. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #1 ** |
| | PLEASE INDICATE AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT. |
| | |
| | 9) NOTE: OK. |
| | |
| | 10) NOTE: OK. |
| | |
| | ** NEW NOTES ** |
| | |
| | 11) NOTE: PLEASE SEE A 4X FEE FOR THE |
| | PLAN REVIEW PORTION OF THE PERMIT FEE |
| | HAS NOW BEEN ASSESSED AS REQUIRED PER FS |
| | 553.80(2)(B). PLEASE KNOW THE FEE OF |
| | $520.68 IS DUE BEFORE PLANS MAY BE |
| | RESUBMITED. |
| | |
| | 12) NOTE: PLEASE KNOW THE PERMIT |
| | APPLICATION WAS NOT IN PACKAGE. PLEASE |
| | BE SURE THE APPLICATION IS BROUGHT BACK |
| | IN. PLEASE ALSO BE SURE THAT THE |
| | ELECTRICLA PERMIT LINE IS SIGNED SO AN |
| | ELECTRICAL PERMIT (GEN-ELEC) PERMIT |
| | NUMBER CAN BE GENERATED FOR THE |
| | ELECTRICALPORTION OF THE GENERATOR |
| | INSTALLATION. |
| | |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |