| Date |
Text |
| 2006-08-03 00:00:00 | ******* UNSAT2ND REVIEW ******** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW WHICH STILL ARE IN NEED OF |
| | ADDRESSING. |
| | |
| | |
| | 1) NOTE: OK. |
| | |
| | 2) NOTE:SAME, PLEASE BE SURE TO HIGH- |
| | LIGHT UNIT. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE THAT THE ATS AS |
| | SHOWN MUST BE "SERVICE ENTRANCE RATED, |
| | CONTAINING A MANUAL MEANS OF DISCONNECT |
| | RATED FOR THE LOAD SERVED ETC |
| | PLEASE "HIGHLIGHT" THE ATS. |
| | 230.70,230.76,230.79 |
| | |
| | 3) NOTE: SAME, PLEASE SEE NO DISCONNECT |
| | SHOWN. |
| | ** PLEASE KNOW, GENERAC NOW HAS A NEW SE |
| | RATED ATS ON THE MARKET WHICH WOULD MEET |
| | THIS AS IT CONTAINS A MANUAL MEANS OF |
| | DISCONNECT FOR THE NORMAL (FPL) SIDE AND |
| | THE EM/GEN FEEDER SIDE. THIS IS NO WAY |
| | SAYING THIS NEW UNIT HAS TO BE USED. |
| | THIS ONLY REQUIRES A DISCONNECTING MEANS |
| | AND DOES NOT REQUIRED OCP. CAN BE A |
| | KNIFE TYPE SWITCH ETC. |
| | |
| | ** PREVIOUS REVIEW NOTE ** PLEASE SEE |
| | MISSING DISCONNECT |
| | FOR FEEDERS FROM GEN GROUPED WITH NEW |
| | MAIN. BRKR INSIDE GEN MAY NOT SERVE AS |
| | THIS DISCONNECT MEANS |
| | 225.31-225.39 |
| | |
| | 4) NOTE: OK. |
| | |
| | 5) NOTE: SAME, HOWEVER PLEASE SEE A NEW |
| | SURVEY IS NOW SHOWN. IF NOT USING THE |
| | ODL ONE, PLEASE REMOVE FROM SETS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE SITE SURVEY SEEMS TO |
| | INDICATE "EASTVIEW ELEC" ?? PLEASE |
| | CLARIFY AND KNOW THAT ALL PLANS AND |
| | PAPERWORK UNDER DARRYL SCHMIDT ELEC |
| | SHALL BE SO STATED. |
| | PLEASE SEE THAT ALL PLANS/DESIGNS |
| | CONTAIN THE PRINTED NAME AND SIGNATURE |
| | OF THE ELECTRICAL CONTRACTOR WHO IS |
| | RESPONSIBEL FOR SAID |
| | DESIGNS.106.1.2,106.3.4.3 |
| | |
| | 6) NOTE:OK. |
| | |
| | 7) NOTE: ** OK, VALUE WAS CHANGED ON |
| | APPLICATION AND FEES ARE OWED BEFORE |
| | PERMIT CAN BE ISSUED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE THE VALUE ON PERMIT |
| | APPLICATION SHALL INCLUDE ALL LABOUR AND |
| | MATERIALS EVEN IF ANY |
| | MATERIALS/EQUIPMENT IS OWNER SUPPLIED. |
| | PLEASE SEE THIS WOULD ALSO INCLUDE THE |
| | VALUE OF THE GAS WORK AS THE GAS |
| | CONTRACTOR IS SIGNED ON. |
| | ** PLEASE KNOW, IF AN APPROPRIATE VALUE |
| | IS NOT STATED, THEN ONE WILL BE ADJUSTED |
| | BY THIS OFFICE USING THE "MARSHALL'S& |
| | SWIFT " GUIDE AS ADOPTED BY THE FBC |
| | ADMINISTRATIVE SECTION 108.3 |
| | |
| | 8) NOTE: SAME, PLEASE SEE ABOVE NOTE |
| | WITH RESPECT TO THE ATS BEING INSTALLED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE INDICATE AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT. |
| | |
| | 9) NOTE: OK. |
| | |
| | 10) NOTE: OK. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |