Plan Review Notes
Plan Review Notes For Permit 06061002
Permit Number 06061002
Review Stop E
Sequence Number 1
Notes
Date Text
2006-06-23 00:00:00******* UNSAT ********
  
  
 1) NOTE: PLEASE SEE THAT AN "EQUIPMENT
 GROUNDING CONDUCTOR" SHALL NOT BE
 INSTALLED UNTIL AFTER THE FIRST MEANS OF
 DISCONNECT. PLEASE SEE
 250.6,250.24B,250.122.
  
 2) NOTE: PLEASE SEE THAT THE ATS AS
 SHOWN MUST BE "SERVICE ENTRANCE RATED,
 CONTAINING A MANUAL MEANS OF DISCONNECT
 RATED FOR THE LOAD SERVED ETC
 PLEASE "HIGHLIGHT" THE ATS.
 230.70,230.76,230.79
  
 3) NOTE: PLEASE SEE MISSING DISCONNECT
 FOR FEEDERS FROM GEN GROUPED WITH NEW
 MAIN. BRKR INSIDE GEN MAY NOT SERVE AS
 THIS DISCONNECT MEANS
 225.31-225.39
  
 4) NOTE: PLEASE INDICATE THE OCP AT GEN
 ON RISER AND PLEASE SHOW GEN.
 215.5.
  
 5) NOTE: PLEASE SEE SITE SURVEY SEEMS TO
 INDICATE "EASTVIEW ELEC" ?? PLEASE
 CLARIFY AND KNOW THAT ALL PLANS AND
 PAPERWORK UNDER DARRYL SCHMIDT ELEC
 SHALL BE SO STATED.
 PLEASE SEE THAT ALL PLANS/DESIGNS
 CONTAIN THE PRINTED NAME AND SIGNATURE
 OF THE ELECTRICAL CONTRACTOR WHO IS
 RESPONSIBEL FOR SAID
 DESIGNS.106.1.2,106.3.4.3
  
 6) NOTE: PLEASE SEE THAT THE GEN
 LOCATION STILL NEEDS TO BE VERIFIED.
 ALL CLEARENCES SHALL BE INDICATED FROM
 HOUSE, WALL, ETC
 PLEASE SEE MECH COMMENTS AND PLEASE ALSO
 BE SURE THE MANUFACTURES SPECS/CUT
 SHEETS INCLUDE THE MIN CLEARENCES AROUND
 EQUIPMENT.
 215.5
  
 7) NOTE: PLEASE SEE THE VALUE ON PERMIT
 APPLICATION SHALL INCLUDE ALL LABOUR AND
 MATERIALS EVEN IF ANY
 MATERIALS/EQUIPMENT IS OWNER SUPPLIED.
 PLEASE SEE THIS WOULD ALSO INCLUDE THE
 VALUE OF THE GAS WORK AS THE GAS
 CONTRACTOR IS SIGNED ON.
 ** PLEASE KNOW, IF AN APPROPRIATE VALUE
 IS NOT STATED, THEN ONE WILL BE ADJUSTED
 BY THIS OFFICE USING THE "MARSHALL'S&
 SWIFT " GUIDE AS ADOPTED BY THE FBC
 ADMINISTRATIVE SECTION 108.3
  
 8) NOTE: PLEASE INDICATE AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT.
  
 9) NOTE: PLEASE INCLUDE ALL CONDUCTORS
 IN RACEWAYS, INCLUDING EQUIPMENT
 GROUNDING CONDUCTORS.
 250.110,250.24B,250.122,240.4,310.16
  
 10) NOTE: PLEASE PROVIDE A LAYOUT FOR
 ALL EQUIPMENT AND LOCATIONS AT DWELLING.
 PLEASE SEE ATS DOES NOT INDICATE FEED TO
 WHAT IS ASSUMED TO BE AN EXISTING PANEL
 SOMEWHERE.
 215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  