| Date |
Text |
| 2006-06-23 00:00:00 | ******* UNSAT ******** |
| | |
| | |
| | 1) NOTE: PLEASE SEE THAT AN "EQUIPMENT |
| | GROUNDING CONDUCTOR" SHALL NOT BE |
| | INSTALLED UNTIL AFTER THE FIRST MEANS OF |
| | DISCONNECT. PLEASE SEE |
| | 250.6,250.24B,250.122. |
| | |
| | 2) NOTE: PLEASE SEE THAT THE ATS AS |
| | SHOWN MUST BE "SERVICE ENTRANCE RATED, |
| | CONTAINING A MANUAL MEANS OF DISCONNECT |
| | RATED FOR THE LOAD SERVED ETC |
| | PLEASE "HIGHLIGHT" THE ATS. |
| | 230.70,230.76,230.79 |
| | |
| | 3) NOTE: PLEASE SEE MISSING DISCONNECT |
| | FOR FEEDERS FROM GEN GROUPED WITH NEW |
| | MAIN. BRKR INSIDE GEN MAY NOT SERVE AS |
| | THIS DISCONNECT MEANS |
| | 225.31-225.39 |
| | |
| | 4) NOTE: PLEASE INDICATE THE OCP AT GEN |
| | ON RISER AND PLEASE SHOW GEN. |
| | 215.5. |
| | |
| | 5) NOTE: PLEASE SEE SITE SURVEY SEEMS TO |
| | INDICATE "EASTVIEW ELEC" ?? PLEASE |
| | CLARIFY AND KNOW THAT ALL PLANS AND |
| | PAPERWORK UNDER DARRYL SCHMIDT ELEC |
| | SHALL BE SO STATED. |
| | PLEASE SEE THAT ALL PLANS/DESIGNS |
| | CONTAIN THE PRINTED NAME AND SIGNATURE |
| | OF THE ELECTRICAL CONTRACTOR WHO IS |
| | RESPONSIBEL FOR SAID |
| | DESIGNS.106.1.2,106.3.4.3 |
| | |
| | 6) NOTE: PLEASE SEE THAT THE GEN |
| | LOCATION STILL NEEDS TO BE VERIFIED. |
| | ALL CLEARENCES SHALL BE INDICATED FROM |
| | HOUSE, WALL, ETC |
| | PLEASE SEE MECH COMMENTS AND PLEASE ALSO |
| | BE SURE THE MANUFACTURES SPECS/CUT |
| | SHEETS INCLUDE THE MIN CLEARENCES AROUND |
| | EQUIPMENT. |
| | 215.5 |
| | |
| | 7) NOTE: PLEASE SEE THE VALUE ON PERMIT |
| | APPLICATION SHALL INCLUDE ALL LABOUR AND |
| | MATERIALS EVEN IF ANY |
| | MATERIALS/EQUIPMENT IS OWNER SUPPLIED. |
| | PLEASE SEE THIS WOULD ALSO INCLUDE THE |
| | VALUE OF THE GAS WORK AS THE GAS |
| | CONTRACTOR IS SIGNED ON. |
| | ** PLEASE KNOW, IF AN APPROPRIATE VALUE |
| | IS NOT STATED, THEN ONE WILL BE ADJUSTED |
| | BY THIS OFFICE USING THE "MARSHALL'S& |
| | SWIFT " GUIDE AS ADOPTED BY THE FBC |
| | ADMINISTRATIVE SECTION 108.3 |
| | |
| | 8) NOTE: PLEASE INDICATE AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT. |
| | |
| | 9) NOTE: PLEASE INCLUDE ALL CONDUCTORS |
| | IN RACEWAYS, INCLUDING EQUIPMENT |
| | GROUNDING CONDUCTORS. |
| | 250.110,250.24B,250.122,240.4,310.16 |
| | |
| | 10) NOTE: PLEASE PROVIDE A LAYOUT FOR |
| | ALL EQUIPMENT AND LOCATIONS AT DWELLING. |
| | PLEASE SEE ATS DOES NOT INDICATE FEED TO |
| | WHAT IS ASSUMED TO BE AN EXISTING PANEL |
| | SOMEWHERE. |
| | 215.5 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |