| Plan Review Notes For Permit 06060985 |
| Permit Number |
06060985 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-06-27 00:00:00 | ***** UNSAT *** | | | | | | 1) NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR FROM EXISTING | | | SERVICE TO NEW PANEL. | | | 250.110,250.122, 680.6 | | | | | | 2) NOTE: PLEASE PROVIDE LOAD | | | CALCULATIONS AND PANEL SCHEDULE OF | | | EXISTING SERVICE WHICH INDICATE THE NEW | | | OCP FOR POOL PANEL AND NEW LOAD ADDED TO | | | EXISTING LOAD. | | | 408.4,220.31 | | | ** PLEASE KNOW, THIS MAY BE PROVIDED BY | | | THE ELECTRICAL CONTRACTOR AND IS NOT | | | REQUIRED BY CURTIS- SINCLAIR. | | | | | | | | | 3) NOTE: PLEASE VERIFY 3-#10'S TO 1HP | | | POOL PUMP. *THIS IS OK, HOWEVER VERIFY | | | AS IF PLANS INDICATE #10, THEN THESE | | | WILL BE REQUIRED. | | | 215.5 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|