| Plan Review Notes For Permit 06060973 |
| Permit Number |
06060973 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-06-30 00:00:00 | NONCOMPLIANT | | | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE VALUE ON THE APPLICATION MUST | | | INCLUDE THE COST OF LABOR AND MATERIAL | | | FOR THE INSTALLATION OF ALL COMPONENTS | | | UNDER THE COPE OF THIS PERMIT. FBC | | | 108.3. | | | | | | 2} PLEASE LOCATE ALL SERVICE EQUIPMENT | | | ON THE PLAN, METER ENCLOSURE, GENERATOR, | | | TRANSFER SWITCH, DISCONNECTS AND PANELS, | | | SO THAT COMPLIANCE WITH ARTICLES 225 AND | | | 230 CAN BE REVIEWED. | | | | | | 3} THE PERSON TAKING RESPONSIBILITY FOR | | | THE DESIGN MUST PRINT AND SIGN THEIR | | | NAME TO SAME PER 106.3.4.2. | | | | | | 4} PROVIDE A LOAD CALCULATIION FOR THE | | | LOAD BEING SERVED BY THE GENERATOR. IF | | | USING 220.35, SHOW THE CALCULATION, NOT | | | JUST WATTHOURS. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|