Plan Review Notes
Plan Review Notes For Permit 06060922
Permit Number 06060922
Review Stop M
Sequence Number 2
Notes
Date Text
2006-10-02 00:00:00*** DENIED ***
 1) SEE ELECTRICAL AND ZONING REVIEW
 NOTES, PLEASE CORRECT.
  
 2) PLEASE BE ADVISED,
 DIESEL GENERATOR EXHUST MUST BE TEN FEET
 AWAY FROM ANY BUILDING OPENINGS
 (WINDOWS, DOORS, ROOF & EAVE VENTS), AND
 TEN FEET AWAY FROM ADJECENT BUILDING
 OPENS. PER 2004 FBC/M 401.5.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  