2006-10-01 00:00:00***UNSAT 2ND REVIEW ***
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW WHICH STILL ARE IN NEED OF
 ADDRESSING.
  
  
 1) NOTE: PLEASE SEE THIS IS A DIESEL
 GENERATOR AND THIS UNIT IS BEING SHOWN
 TOO CLOSE TO TO THE BUILDING AS SHOWN
 FOR MIN CLEARENCES REQUIRED. PLEASE SEE
 THERE WILL BE MECHANICAL COMMENTS. THE
 10FT OR MIN MIN FOR DIESEL FUEL TYPE IF
 FROM ALL OPENINGS, NOT ONLY WINDOWS.
 (SOFFIT ETC0. PLEASE SEE DUE TO THE 10FT
 SETS BACK AND THE MIN REQUIRED FROM
 PROPERTY LINE , FROM BUILIDING, AND THE
 WITH OF THE GEN, A NEW LOCATION MUST BE
 PROPOSED.
 PLEASE SEE NO INFORMATION FROM
 MANUAFATURE WAS SUBMITTED WHICH
 INDICATES THE MIN REQUIRED CLEARENCE ALL
 THE WAY AROUND UNIT. IT IS KNOWN FROM
 THIS MANUFACTURE , TYPICALLY IS REQUIRES
 3FT (MIN) SOME ARE 5FT).
 WITH THAT SAID, IF THE GEN IS 3FT FROM
 HOUSE AND ZONING DOES NOT PERMIT THIS
 UNIT CLOSER THAT 6',1" FROM PROPOERTY
 THIS WILL NOT WORK.
  
  
 ** PLEASE KNOW, SITE SURVEY AS STAMPED
 FROM ZONING HAS BEEN "VOIDED".
  
 2) NOTE: PLEASE COMPLETE RISER DIAGRAM.
 AS SHOWN, THERE SEEM TO BE A SUB PANEL
 WHICH IS BEING FED FROMTHE EXISTING
 200A PANEL, THROUGH THE ATS, YET THIS IS
 NOT SHOWN ON RISER, WITH CONDUCTORS ETC.
 PLEASE SEE MISSING CONDUIT, EQUIPMENT
 GROUNDING CONDUCTORS, ETC.
 PLEASE PROVIDE A COMPLETE OVERVIEW OF
 ALL EQUIPMENT AND LOCATIONS.
 PLEASE KNOW, AS PER 225.31-225.39, AND
 WHAT HOW THE 2005 (FUTURE) CODE INTENDS,
 THE BRKR ON THE GEN MUST BE WITH
 INSIGHT, READILY ACCESSIBLE, AND THER
 MUST BE A DEADFRONT WHEN ACCESSING THE
 GEN. 110.27.
 SIGNAGE FOR ALL WILL ALSO BE REQUIRED AS
 THESE DISONNECTING MEANS ARE NOT
 GROUPED.
 225.34,230.72,230.2,702.8 ETC
  
  
 3) NOTE: PLEASE SUBMIT PLANS DONE IN
 DRAFTSMAN LIKE QUALITY AS REQUIRED UNDER
 THE FBC 106.1.
 PLEASE SEE PEN/PENCIL PLANS ARE NOT
 PERMITTED AND WHITE OUT IS ALSO NOT
 ACCEPTABLE.
 PLEASE ALSO SEE AS PREVIOUSLY REQUESTED,
 PLEASE BE SURE THE PRINTED NAME AND
 SIGNTURE OF THE PRESON RESPONSIBLE FOR
 PLANS/DESIGN/LOADS ETC IS CLEARLY SHOWN
 ON ALL SHEETS. (EXCEPT MANUFACTURE
 SHEETS FOR EQUIPMENT ).
  
 4)NOTE: PLEASE SEE THE SPECS AS
 SUBMITTED ON GEN DO NOT CLEARLY INDICATE
 WHICH UNIT IS BEING PROPOSED.
 PLEASE SEE LOAD IN LOAD CALCS SEEM TO
 EXCEED RATINGS ON SPEC SHEETS.
 PLEASE ALSO BE SURE THE SPECS SHEETS
 CORRELATE WITH THE RISER WHICH INDICATES
 100A OCP AT THE GEN.
 110.3,240,220,90.7 ETC.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717