| Date |
Text |
| 2006-06-23 00:00:00 | ********* UNSAT ********** |
| | |
| | 1) NOTE: PLEASE SUBMIT A COMPLETE |
| | ELECTRICAL RISER DIAGRAM SHOWING |
| | LOCATIONS OF ALL ELECTRICAL EQUIPMENT. |
| | PLEASE SHOW A LAYOUT ON A SHEET FOR THE |
| | LOCATIONS OF ALL ALSO. |
| | 215.5 |
| | PLEASE SEE 230.70,230.72,230.76,230.79, |
| | 225.31-225.39 |
| | MISSING DISCONNECTS, GROUPING ETC. |
| | |
| | 2) NOTE: PLEASE INDICATE IF THE PANEL |
| | SCHEDULE SHOWN IS A NEW EM SUB PANEL.? |
| | 215.5 |
| | |
| | 3) NOTE: PLEASE SEE HEAT LOAD SHOWS |
| | 7.5KW , YET CALCS INDICATE 6KW? |
| | PLEASE ALSO SEE IF THIS IS THE MAIN |
| | EXISTING PANEL, WHERE ARE ALL OTHER |
| | LOADS? IF ALL OTHERS ARE GAS OR ARE DONE |
| | BY LOAD SHEEDING PLEASE INDICATE. |
| | 215.5,702.5,220.31 |
| | |
| | 4) NOTE: PLEASE CORRELATE RISER OCP AT |
| | GEN WITH SPECS OF GEN. |
| | 215.5 |
| | **PLEASE SEE 240.6 FOR STANDARD OCP. |
| | |
| | 5) NOTE: PLEASE SUBMIT ALL SPECS FOR ALL |
| | , INCLUDING NEW ATS. PLEASE SEE WE ARE |
| | UNABLE TO VERIFY AT THIS TIME AS THE |
| | SPECS WERE NOTE SUBMITTED. |
| | |
| | ** PLEASE ALSO BE SURE SPECS FOR GEN |
| | INDICATE THE MIN CLEARENCES REQUIRED PER |
| | MANUFACTURE. |
| | |
| | 6) NOTE: PLEASE KNOW, ALL SHEETS SHALL |
| | CONTAIN THE PRINTED NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR PLANS. |
| | ** PLEASE KNOW, THESE ARE NOT REQUIRED |
| | TO BE NOTORIZED, HOWEVER "IF" THEY ARE |
| | NOTORIZED, THEN THEY MUST BE DONE |
| | CORRECTLY AS REQUIRED UNDER FS 117.05. |
| | PLEASE SEE THAT A RUBBER STAMP AND |
| | SIGNATURE FROM NOTORY IS NOT ACCEPTABLE |
| | NOR IS IT LEGAL TO DO SO. |
| | (ONCE AGAIN, THESE ARE NOT REQUIRED TO |
| | BE). |
| | |
| | 7) NOTE: PLEASE SEE ZONING COMMENTS AND |
| | PLEASE PROVIDE ALL DIMENSIONS FOR GEN |
| | ETC WITH ALL SETBACKS ETC FROM HOUSE AND |
| | PROPERTY LINES. |
| | |
| | |
| | 8) NOTE: PLEASE SEE BLDG COMMENTS AS THE |
| | THICKNESS OF THE GEN SLAB SHALL BE |
| | INDICATED. |
| | |
| | 9) NOTE: PLEASE KNOW, IF IT IS TYHE |
| | INENT FOR THE ELECTRICAL CONT TO ALSO |
| | HOOK UP ALL ELECTRICAL , THEN PLEASE BE |
| | SURE TO SIGN ON THE ELECTRICAL LINE ON |
| | PERMIT APPLICATION SO THAT AN ELECTRICAL |
| | PERMIT CAN BE GENERATED. THIS SHOULD BE |
| | DONE BY THE QUALIFIER WHEN RESUBMITTING |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |