Plan Review Notes
Plan Review Notes For Permit 06060922
Permit Number 06060922
Review Stop E
Sequence Number 1
Notes
Date Text
2006-06-23 00:00:00********* UNSAT **********
  
 1) NOTE: PLEASE SUBMIT A COMPLETE
 ELECTRICAL RISER DIAGRAM SHOWING
 LOCATIONS OF ALL ELECTRICAL EQUIPMENT.
 PLEASE SHOW A LAYOUT ON A SHEET FOR THE
 LOCATIONS OF ALL ALSO.
 215.5
 PLEASE SEE 230.70,230.72,230.76,230.79,
 225.31-225.39
 MISSING DISCONNECTS, GROUPING ETC.
  
 2) NOTE: PLEASE INDICATE IF THE PANEL
 SCHEDULE SHOWN IS A NEW EM SUB PANEL.?
 215.5
  
 3) NOTE: PLEASE SEE HEAT LOAD SHOWS
 7.5KW , YET CALCS INDICATE 6KW?
 PLEASE ALSO SEE IF THIS IS THE MAIN
 EXISTING PANEL, WHERE ARE ALL OTHER
 LOADS? IF ALL OTHERS ARE GAS OR ARE DONE
 BY LOAD SHEEDING PLEASE INDICATE.
 215.5,702.5,220.31
  
 4) NOTE: PLEASE CORRELATE RISER OCP AT
 GEN WITH SPECS OF GEN.
 215.5
 **PLEASE SEE 240.6 FOR STANDARD OCP.
  
 5) NOTE: PLEASE SUBMIT ALL SPECS FOR ALL
 , INCLUDING NEW ATS. PLEASE SEE WE ARE
 UNABLE TO VERIFY AT THIS TIME AS THE
 SPECS WERE NOTE SUBMITTED.
  
 ** PLEASE ALSO BE SURE SPECS FOR GEN
 INDICATE THE MIN CLEARENCES REQUIRED PER
 MANUFACTURE.
  
 6) NOTE: PLEASE KNOW, ALL SHEETS SHALL
 CONTAIN THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR PLANS.
 ** PLEASE KNOW, THESE ARE NOT REQUIRED
 TO BE NOTORIZED, HOWEVER "IF" THEY ARE
 NOTORIZED, THEN THEY MUST BE DONE
 CORRECTLY AS REQUIRED UNDER FS 117.05.
 PLEASE SEE THAT A RUBBER STAMP AND
 SIGNATURE FROM NOTORY IS NOT ACCEPTABLE
 NOR IS IT LEGAL TO DO SO.
 (ONCE AGAIN, THESE ARE NOT REQUIRED TO
 BE).
  
 7) NOTE: PLEASE SEE ZONING COMMENTS AND
 PLEASE PROVIDE ALL DIMENSIONS FOR GEN
 ETC WITH ALL SETBACKS ETC FROM HOUSE AND
 PROPERTY LINES.
  
  
 8) NOTE: PLEASE SEE BLDG COMMENTS AS THE
 THICKNESS OF THE GEN SLAB SHALL BE
 INDICATED.
  
 9) NOTE: PLEASE KNOW, IF IT IS TYHE
 INENT FOR THE ELECTRICAL CONT TO ALSO
 HOOK UP ALL ELECTRICAL , THEN PLEASE BE
 SURE TO SIGN ON THE ELECTRICAL LINE ON
 PERMIT APPLICATION SO THAT AN ELECTRICAL
 PERMIT CAN BE GENERATED. THIS SHOULD BE
 DONE BY THE QUALIFIER WHEN RESUBMITTING
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved