| Date |
Text |
| 2006-06-22 00:00:00 | ******DENIED****** |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR PLAN REVIEW FOR A GAS PERMIT: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE, |
| | THE REGULATORS, SHUT OFF VALVES, AND |
| | CORRESPONDING LENGTHS PER FBC-2004 FUEL |
| | GAS CODE. |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, AND ALL PIPE SIZES. |
| | 3. TYPE OF GAS, (LP OR NATURAL) PLEASE |
| | INDICATE THIS ON DRAWINGS. |
| | 4. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33).(NOTE: THIS INCLUDES THE |
| | EXISTING SYSTEM BTU'S ALONG WITH THE |
| | GENERATOR BTU'S, PLEASE INDICATE THE |
| | TOTAL BTU LOAD ON THE DRAWING) |
| | 5. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4).(NOTE: THIS |
| | INCLUDES THE EXISTING SYSTEM, FROM WHAT |
| | I READ IN YOUR NOTES IT APPEARS THE |
| | LONGEST LENGTH IS 120', PLEASE INDICATE |
| | THIS ON THE DRAWING) |
| | 6. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2(NOTE: |
| | NEED MANUFACTURER CUT SHEET OF THE TYPE |
| | OF REGULATOR BEING USED) |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| | RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. PLEASE SEE THE ATTACHED CITY OF |
| | WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS FOR REFERENCE ON RESUBMIT- |
| | TAL AND FUTURE PERMIT APPLICATIONS. |
| | PLEASE SEE CORRECTED DRAWING IN RED INK |
| | FOR REFERENCE FOR RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |
| | |
| | |
| | |
| | |
| | |
| | |