Plan Review Notes
Plan Review Notes For Permit 06060920
Permit Number 06060920
Review Stop G
Sequence Number 1
Notes
Date Text
2006-06-22 00:00:00******DENIED******
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLAN REVIEW FOR A GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE,
 THE REGULATORS, SHUT OFF VALVES, AND
 CORRESPONDING LENGTHS PER FBC-2004 FUEL
 GAS CODE.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, AND ALL PIPE SIZES.
 3. TYPE OF GAS, (LP OR NATURAL) PLEASE
 INDICATE THIS ON DRAWINGS.
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).(NOTE: THIS INCLUDES THE
 EXISTING SYSTEM BTU'S ALONG WITH THE
 GENERATOR BTU'S, PLEASE INDICATE THE
 TOTAL BTU LOAD ON THE DRAWING)
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).(NOTE: THIS
 INCLUDES THE EXISTING SYSTEM, FROM WHAT
 I READ IN YOUR NOTES IT APPEARS THE
 LONGEST LENGTH IS 120', PLEASE INDICATE
 THIS ON THE DRAWING)
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2(NOTE:
 NEED MANUFACTURER CUT SHEET OF THE TYPE
 OF REGULATOR BEING USED)
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. PLEASE SEE THE ATTACHED CITY OF
 WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS FOR REFERENCE ON RESUBMIT-
 TAL AND FUTURE PERMIT APPLICATIONS.
 PLEASE SEE CORRECTED DRAWING IN RED INK
 FOR REFERENCE FOR RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved