| Plan Review Notes For Permit 06060909 |
| Permit Number |
06060909 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-06-23 00:00:00 | **** UNSAT **** | | | | | | | | | 1) NOTE: PLEASE BE SURE THE PRINTED NAME | | | AND SIGNATURE IS ON PLANS FOR THE PERSON | | | REPSONSIBLE FOR PLANS. | | | FBC 106.2.1 | | | | | | 2) NOTE: PLEASE KNOW, LOCATION OF | | | HOUSE/GEN IS IN A "A" FLOOD ZONE AND | | | PLANS SHALL INDICATE EQUIPMENT AT 6" | | | MIN ABOVE THE BFE. | | | | | | 3) NOTE: PLEASE PROVIDE A LAYOUT FOR ALL | | | EQUIPMENT AS VERIFICATION OF THE | | | GROUPING OF THE MAINS AND DISCONECT CAN | | | NOT BE DONE AT THIS TIME. | | | 230.72,225.34 | | | | | | PLEASE SEE BLDG COMMENTS AS SLAB DETAIL | | | FOR GEN IS MISSING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|