| Date |
Text |
| 2006-08-05 00:00:00 | *** UNSAT 2ND REVIEW *** |
| | |
| | 1) NOTE: PLEASE SEE NOTE FROM PREVIOUS |
| | REVIEW. PLEASE SEE FBC CHAPTER 13, AS |
| | THE SPACE IS IN A BUILDING LARGER THAN |
| | 5K SQ FT. PLEASE SEE 13-415.1.ABC.1.1, |
| | .1.2, .1.3. |
| | THIS SPACE IS NOT A BUILDING. PLEASE SEE |
| | ELECTRICAL IS FED FROM A SERVICE WHICH |
| | FEEDS ONE BUILDING. PLEASE SEE FBC |
| | DEFINITIONS OF BUILDINGS. IF THIS SPACE |
| | WAS SEPARATED BY A "FIRE WALL" ON BOTH |
| | SIDES WHICH REQUIRES 4HR SEPARATION AND |
| | ALSO REQUIRES COMPLETE COLLAPSE OF THE |
| | ADOINING ROOFS WITH OUT AFFECTTING THE |
| | STRUCTURAL INTEGRITY OF THE BUILDING |
| | ETC. |
| | PLEASE SEE AT THIS POINT THE SPACE WOULD |
| | BE CONSIDERED A BUILDING AND A SEPARATE |
| | ELECTRICAL SERVICE WOULD BE REQUIRED. |
| | |
| | ** PLEASE SEE SPACE #11&12 SEEM TO BE |
| | EXISTINGWITH ONLY THE NEW SEPARATION |
| | BEING ADDED, IF SO PLEASE LABEL ALL |
| | ELECTRICAL OR CLOUD SPACE AS EXISTING. |
| | PLEASE SEE SPACE #13&14 WILL REQUIRE NEW |
| | CONTROLS PER CHAPTER 13 AS NOTED. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |