| Plan Review Notes For Permit 06060899 |
| Permit Number |
06060899 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-06-27 00:00:00 | ***DENIED*** | | | | | | 1) LIFE SAFETY SHALL COMPLY WITH NFPA | | | 101, 2003 EDITION. | | | | | | 2) A FIRE EXTINGUISHER IS SHOWN IN | | | RECEPTION (1). A 2A-10B,C RATED FIRE | | | EXTINGUISHER IS ALSO REQUIRED IN OTHER | | | TENANT SPACE DUE TO THE SEPARATION. | | | | | | 3) CONSTRUCTION, ALTERATION AND | | | DEMOLITION SHALL COMPLY WITH NFPA 241. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|