| Plan Review Notes For Permit 06060867 |
| Permit Number |
06060867 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-07-10 00:00:00 | DENIED | | | | | | 1) THE ROOFING SYSTEM SPECIFIED ON PAGE | | | 40 OF THE MULE-HIDE PRODUCT NOA HAS A | | | MAXIMUM DESIGN PRESSURE OF -60 PSF. THIS | | | PRESSURE IS TO LOW FOR ZONE 3 (CORNERS). | | | GENERAL LIMITATION #7 ON PAGE 43 OF THE | | | NOA ALLOWS THE CORNERPRESSURES TO BE | | | INCREASED BY INCREASING THE FASTENER | | | DENSITIES USING THE CALCULATIONS | | | SPECIFIED IN (RAS 117) ROOFING | | | APPLICATION STANDARD 117. HOWEVER, | | | GENERAL LIMITATION #7 ON THIS NOA | | | REQUIRES THESE RAS 117 CALCULATIONS TO | | | BE PREPARED, SIGNED AND SEALED BY A | | | FLORIDA REGISTERED ENGINEER, ARCHITECT | | | OR REGISTERED ROOF CONSULTANT. PLEASE | | | SUBMIT TWO COPIES OF SIGNED AND SEALED | | | RAS 117 CALCULATIONS FOR THIS SYSTEM. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|