| 2006-06-15 00:00:00 | DENIED | | | | | | 1) THE ROOFING ASSEMBLY SELECTED FROM | | | THE NOA (PAGE 35) FOR THE MULE HIDE | | | BITUMEN ROOF SYSTEM HAS A DESIGN | | | PRESSURE OF -45 PSF WHICH IS TOO LOW AND | | | IS NOT ALLOWED TO BE INCREASED. SEE | | | LIMITATION #9 ON PAGE 43. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|