| 2006-06-24 00:00:00 | *********UNSAT ************ |
| | |
| | 1) NOTE: PLEASE SEE ALL SETS OF PLANS |
| | ARE SIGNED, DATED OR SEALED BY THE |
| | DESIGN PROFESSIONAL OF RECORD AS SHOWN |
| | ON TITLE BLOCKS. PER FS471.025 |
| | PLEASE ALSO SEE ALL SHEETS NOT DONE BY |
| | THE PE, SHALL CONTAN THE PRINTED NAME |
| | AND SIGNATURE OF THE PERSON RESPOSIBLE |
| | FOR PLANS/DESIGN. |
| | FBC 106.1.2,106.1.3 ADMIN SECT AS |
| | ADOPTED BY THE CITY OF WEST PALM BEACH. |
| | |
| | 2) NOTE: PELASE SEE PLANS MENTIONS NEW |
| | SPLIT A/C SYSTEM REPLACING OLD SYSTEM, |
| | HOWEVE NO NEW CIRCUIT(S) OR LAODS ARE |
| | SHOWN ON PANEL SCHEDULE. |
| | PLEASE INDICATE LOAD CALCULATIONS PER |
| | 220.31B. |
| | ** PLEASE SEE LOAD CALCULATIONS ALREADY |
| | SHOW LOAD AT 146 A'S, AND THEY DON'T |
| | INLCUDE NEWA/C LOADS AS SHOWN. PLEASE |
| | KNOW, IT APPEARS A NEW SERVICE UPGRADE |
| | WILL BE REQUIRED . PLEASE ALSO SEE 90.8 |
| | AS THE CODE ALSO REQUIRES ROOM FOR |
| | FUTURE EXPANSION. |
| | 3) NOTE: PLEASE SHOW SD'SIN EXISTIGN |
| | DWELLING EXISTING WHICH MEET CURRENT |
| | CODE OR NEW TO BE INSTALLED. |
| | FBC 2004/ RES R313, NFPA-72 11.5.1.1, |
| | 11.8.3 |
| | |
| | 4) NOTE: PLEASE SEE MIN CLEARENCES SHALL |
| | BE INDICATED FOR CLOSET LTS. PLEASE KNOW |
| | A MIN OF 18" SHELVING SHALL BE USEDAND |
| | ASSUMED PER 410.8 |
| | |
| | 5) NOTE: PLEASE SEE PLANS INDICATE NEW |
| | COMPUTER RM, YET IS ELEC NEW OR |
| | EXISTING? 210.52,210.70 ETC |
| | |
| | 6) NOTE: PLEASE SEE BUIDLING REVIEW |
| | NOTES AS THE VALUE SHALL BE UPDATED. |
| | 108.3 |
| | |
| | ** PLEASE SUBMIT TWO COMPLETE SETS WITH |
| | ALL SHEET ATTACHED INTO SETS AND NOT |
| | LOOSE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |