Plan Review Notes
Plan Review Notes For Permit 06060845
Permit Number 06060845
Review Stop B
Sequence Number 1
Notes
Date Text
2006-06-15 00:00:00DENIED
  
 1) SPEICFY THE MEAN ROOF HEIGHT OF THE
 STRUCTURE ON THE PERMIT APPLICATION.
  
 2) SYSTEM SPECIFIED IN NOA HAS A DESIGN
 PRESSURE OF -75 PSF. PROVIDE RAS 117
 CALCULATIONS AS REQUIRED BY LIMITATION
 #7 ON PAGE 16 OF THE NOA.
  
 3) BASE SHEET MUST BE ATTACHED USING ONE
 OF THE FASTENERS SPECIFIED IN THE NOA.
 THE OLYLOK FASTENER IS NOT ONE OF THEM.
 SEE FASTENING ON PAGE 12 OF NOA.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  