| Plan Review Notes For Permit 06060845 |
| Permit Number |
06060845 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-06-15 00:00:00 | DENIED | | | | | | 1) SPEICFY THE MEAN ROOF HEIGHT OF THE | | | STRUCTURE ON THE PERMIT APPLICATION. | | | | | | 2) SYSTEM SPECIFIED IN NOA HAS A DESIGN | | | PRESSURE OF -75 PSF. PROVIDE RAS 117 | | | CALCULATIONS AS REQUIRED BY LIMITATION | | | #7 ON PAGE 16 OF THE NOA. | | | | | | 3) BASE SHEET MUST BE ATTACHED USING ONE | | | OF THE FASTENERS SPECIFIED IN THE NOA. | | | THE OLYLOK FASTENER IS NOT ONE OF THEM. | | | SEE FASTENING ON PAGE 12 OF NOA. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|