Plan Review Notes
Plan Review Notes For Permit 06060814
Permit Number 06060814
Review Stop E
Sequence Number 1
Notes
Date Text
2006-06-29 00:00:00********** UNSAT **********
  
 1) NOTE: PLEASE SEE PLANS SPECIFICALLY
 STATE THE 2001 FBC IN MANY LOCATIONS
 WHERE-AS WE ARE CURRENTLY UNDER THE 2004
 FBC.
 PLEASE ALSO NOTE ELECTRICAL PER
 NFPA-70(NEC) 2002.
  
 2) NOTE: PLEASE SEE A MEANS OF
 DISCONNECT IS REQUIRED FOR CIRCUIT AT
 NEW STRUCTURE. THIS CAN BE A TOGGLE/SNAP
 SWITCH. 225.31-225.39
  
 3) NOTE: PLEASE SEE 250.32, AS NEW
 FOOTER STEEL IS REQUIRED TO BE BONDED
 UNLES MEETING EXCEPTION OF A SINGLE 120V
 CIRCUIT W/ GFI PROTECTION. PLEASE EITHER
 ADD THE GROUNDING ELECTRODE SYSTEM, OR
 INDICATE THE GFI PROTECTION FOR THE ONE
 CIRCUIT.
  
 4) NOTE: PLEASE SEE BUIDLING REVIEW
 COMMENTS, AS THE TRUSS SUBMITTIAL
 PACKAGE INCLUDE CLEARLY TWO DIFFERENT
 SIGNATURES FOR THE ENGINEER.
 PLEASE ALSO SEE SET WHICH IS
 PHOTO-COPIED. PLEASE KNOW, ALL SETS
 SHALL BE SIGNED, DATED AND SEAL WITH
 ORIGINAL SIGNATURE AND RAISED SEAL.
 FAC 61G15-23.002, FS 471.025
 THIS IS ONLY NOTED BY THIS REVIEWER AND
 IS NOT PART OF THE REVIEW OF THE
 ELECTRICAL SHEETS BY THE ARCHITECT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  