| Date |
Text |
| 2006-06-29 00:00:00 | ********** UNSAT ********** |
| | |
| | 1) NOTE: PLEASE SEE PLANS SPECIFICALLY |
| | STATE THE 2001 FBC IN MANY LOCATIONS |
| | WHERE-AS WE ARE CURRENTLY UNDER THE 2004 |
| | FBC. |
| | PLEASE ALSO NOTE ELECTRICAL PER |
| | NFPA-70(NEC) 2002. |
| | |
| | 2) NOTE: PLEASE SEE A MEANS OF |
| | DISCONNECT IS REQUIRED FOR CIRCUIT AT |
| | NEW STRUCTURE. THIS CAN BE A TOGGLE/SNAP |
| | SWITCH. 225.31-225.39 |
| | |
| | 3) NOTE: PLEASE SEE 250.32, AS NEW |
| | FOOTER STEEL IS REQUIRED TO BE BONDED |
| | UNLES MEETING EXCEPTION OF A SINGLE 120V |
| | CIRCUIT W/ GFI PROTECTION. PLEASE EITHER |
| | ADD THE GROUNDING ELECTRODE SYSTEM, OR |
| | INDICATE THE GFI PROTECTION FOR THE ONE |
| | CIRCUIT. |
| | |
| | 4) NOTE: PLEASE SEE BUIDLING REVIEW |
| | COMMENTS, AS THE TRUSS SUBMITTIAL |
| | PACKAGE INCLUDE CLEARLY TWO DIFFERENT |
| | SIGNATURES FOR THE ENGINEER. |
| | PLEASE ALSO SEE SET WHICH IS |
| | PHOTO-COPIED. PLEASE KNOW, ALL SETS |
| | SHALL BE SIGNED, DATED AND SEAL WITH |
| | ORIGINAL SIGNATURE AND RAISED SEAL. |
| | FAC 61G15-23.002, FS 471.025 |
| | THIS IS ONLY NOTED BY THIS REVIEWER AND |
| | IS NOT PART OF THE REVIEW OF THE |
| | ELECTRICAL SHEETS BY THE ARCHITECT. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |