Plan Review Notes
Plan Review Notes For Permit 06060814
Permit Number 06060814
Review Stop B
Sequence Number 1
Notes
Date Text
2006-08-02 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06060814
 ADD: 1041 45TH ST
 CONT: ATLANTIC GENNERAL CONT
 TEL: (561)718-2668
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) SHEET 1& 2 BOTH MAKE REFRENCE TO THE
 FBC 2001, PLANS SUBMITTED AFTER
 SEPT.30TH, 2005 FOR PERMIT ARE REQUIRED
 TO BE DESIGNED TO THE 2004 FBC FL S S
 553.
  
 3)SHEET# 1 INDICATES THE DESIGNED THIS
 STRUCTURE TO ASCE 7-02, EXP "B".MISSING
 THE ITEM # 4 PRESSURE COEFFICIENT.
 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 4) SHEET# 2 BEAM DETAIL INDICATES BEAM
 SIZE AND (9)# 5 BARS BUT NO INFORMATION
 AS TO STIRRUP SIZE OR SPACING.
  
 5) PLANS ARE MISSING TEMITE
 TREATMENT.1816.1 TERMITE PROTECTION.
 TERMITE PROTECTION SHALL BE PROVIDED BY
 REGISTERED TERMITICIDES, INCLUDING SOIL
 APPLIED PESTICIDES, BAITING SYSTEMS, AND
 PESTICIDES APPLIED TO WOOD, OR OTHER
 APPROVED METHODS OF TERMITE PROTECTION
 LABELED FOR USE AS A PREVENTATIVE
 TREATMENT TO NEW CONSTRUCTION. SEE
 SECTION 202 , REGISTERED TERMITICIDE.
 UPON COMPLETION OF THE APPLICATION OF
 THE TERMITE PROTECTIVE TREATMENT, A
 CERTIFICATE OF COMPLIANCE SHALL BE
 ISSUED TO THE BUILDING DEPARTMENT BY THE
 LICENSED PEST CONTROL COMPANY THAT
 CONTAINS THE FOLLOWING STATEMENT: ?THE
 BUILDING HAS RECEIVED A COMPLETE
 TREATMENT FOR THE PREVENTION OF
 SUBTERRANEAN TERMITES. TREATMENT IS IN
 ACCORDANCE WITH RULES AND LAWS
 ESTABLISHED BY THE FLORIDA DEPARTMENT OF
 AGRICULTURE AND CONSUMER SERVICES.?
  
 6) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 G ) SQ. FT. FOOTPRINT
 H) FLOOD ZONE (AH)
 I) FLOOD ELEVATION(17.5')MINIMUM
  
 7)NOTE:PROVIDE FLOOD ZONE ELEVATION
 CERTIFICATE FOR NEW CONSTRUTION WITH
 BASE FLOOD ELEVATION, CITY CODE REQUIRES
 AN ADDITIONAL 6".(17.5')
  
 8) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 9) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 10) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) TRUSS ANCHORS
 B) ROOFING ASSEMBLIES
  
 11) 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERMORMED IN A MANNER
 SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS
 SUCH ACTIVITY IS PERMITTED TO AFFECT
 SAID PROPERTY PURSUANT TO A CONSENT BY
 THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER.THIS INCLUDES
 BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY
 SHALL NOT ADVERSELY IMPACT HISTORIC
 SURFACE WATER DRAINAGE FLOWS SERVING
 ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES.
 ACCORDINGLY, DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF
 PERMEABLE LAND AREA ON ANY PARCELL SHALL
 AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN
 CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 12) 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 13) PLANS DO NOT INDICATE WHAT TYPE OF
 PAPER BACK LATH WILL BE USED ON THE
 CEILING OR LENGTH OR TYPE OF NAIL.
 2510 LATHING FOR CEMENT PLASTER (STUCCO)
  
 2510.3 INSTALLATION.
 INSTALLATION OF THESE MATERIALS SHALL BE
 IN COMPLIANCE WITH ASTM C 926 AND ASTM C
 1063.
  
 14) PLANS DO NOT INDICATE COMPLIANCE
 WITH ATTIC VENTILATION, 1203.2.
  
 15) PLANS INDICATE THAT THIS PAVILION IS
 LOCATED IN A ISLAND OF A PARKING LOT.
 PLEASE PROVIDE THE ACCESSIBLE ACCESS TO
 THE PAVILION, INDICATE AN ACCESSIBLE
 CROSS WALK, CURB CUTS AND DETECTABLE
 WARNING AT CROSSWALKS.
  
 11-4.3.2 (2)AT LEAST ONE ACCESSIBLE
 ROUTE SHALL CONNECT ACCESSIBLE
 BUILDINGS, FACILITIES, ELEMENTS, AND
 SPACES THAT ARE ON THE SAME SITE.
  
 11-4.3.8AT LEAST ONE ACCESSIBLE ROUTE
 SHALL CONNECT ACCESSIBLE BUILDINGS,
 FACILITIES, ELEMENTS, AND SPACES THAT
 ARE ON THE SAME SITE.
  
 11-4.3.6 SURFACE TEXTURES.
 THE SURFACE OF AN ACCESSIBLE ROUTE SHALL
 COMPLY WITH SECTION 11-4.5 .
  
 11-3.5 MARKED CROSSING. A CROSSWALK OR
 OTHER IDENTIFIED PATH INTENDED FOR
 PEDESTRIAN USE IN CROSSING A VEHICULAR
 WAY.
  
 11-4.7.1 LOCATION.
 CURB RAMPS COMPLYING WITH SECTION 11-4.7
 SHALL BE PROVIDED WHEREVER AN ACCESSIBLE
 ROUTE CROSSES A CURB.
 CURB RAMPS MUST BE LOCATED OUTSIDE OF
 DISABLED PARKING SPACES AND ACCESS
 AISLES.
  
 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026