| 2006-08-02 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 06060814 |
| | ADD: 1041 45TH ST |
| | CONT: ATLANTIC GENNERAL CONT |
| | TEL: (561)718-2668 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) SHEET 1& 2 BOTH MAKE REFRENCE TO THE |
| | FBC 2001, PLANS SUBMITTED AFTER |
| | SEPT.30TH, 2005 FOR PERMIT ARE REQUIRED |
| | TO BE DESIGNED TO THE 2004 FBC FL S S |
| | 553. |
| | |
| | 3)SHEET# 1 INDICATES THE DESIGNED THIS |
| | STRUCTURE TO ASCE 7-02, EXP "B".MISSING |
| | THE ITEM # 4 PRESSURE COEFFICIENT. |
| | 2004 FL. BLD CODE 1603.1.4 THE |
| | FOLLOWING INFORMATION RELATED TO WIND |
| | SHALL BE SHOWN ON THE CONSTRUCTION |
| | DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 4) SHEET# 2 BEAM DETAIL INDICATES BEAM |
| | SIZE AND (9)# 5 BARS BUT NO INFORMATION |
| | AS TO STIRRUP SIZE OR SPACING. |
| | |
| | 5) PLANS ARE MISSING TEMITE |
| | TREATMENT.1816.1 TERMITE PROTECTION. |
| | TERMITE PROTECTION SHALL BE PROVIDED BY |
| | REGISTERED TERMITICIDES, INCLUDING SOIL |
| | APPLIED PESTICIDES, BAITING SYSTEMS, AND |
| | PESTICIDES APPLIED TO WOOD, OR OTHER |
| | APPROVED METHODS OF TERMITE PROTECTION |
| | LABELED FOR USE AS A PREVENTATIVE |
| | TREATMENT TO NEW CONSTRUCTION. SEE |
| | SECTION 202 , REGISTERED TERMITICIDE. |
| | UPON COMPLETION OF THE APPLICATION OF |
| | THE TERMITE PROTECTIVE TREATMENT, A |
| | CERTIFICATE OF COMPLIANCE SHALL BE |
| | ISSUED TO THE BUILDING DEPARTMENT BY THE |
| | LICENSED PEST CONTROL COMPANY THAT |
| | CONTAINS THE FOLLOWING STATEMENT: ?THE |
| | BUILDING HAS RECEIVED A COMPLETE |
| | TREATMENT FOR THE PREVENTION OF |
| | SUBTERRANEAN TERMITES. TREATMENT IS IN |
| | ACCORDANCE WITH RULES AND LAWS |
| | ESTABLISHED BY THE FLORIDA DEPARTMENT OF |
| | AGRICULTURE AND CONSUMER SERVICES.? |
| | |
| | 6) 110.2* W. P. B. ADMINISTRATIVE CODE, |
| | INFORMATION THAT IS REQUIRED FOR RECORD |
| | KEEPING & FOR CERTIFICATE OF OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PERMIT WAS ISSUED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. |
| | D) THE DESIGN OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| | IS REQUIRED. |
| | F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| | OF THE BUILDING PERMIT. |
| | G ) SQ. FT. FOOTPRINT |
| | H) FLOOD ZONE (AH) |
| | I) FLOOD ELEVATION(17.5')MINIMUM |
| | |
| | 7)NOTE:PROVIDE FLOOD ZONE ELEVATION |
| | CERTIFICATE FOR NEW CONSTRUTION WITH |
| | BASE FLOOD ELEVATION, CITY CODE REQUIRES |
| | AN ADDITIONAL 6".(17.5') |
| | |
| | 8) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 9) WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 10) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) TRUSS ANCHORS |
| | B) ROOFING ASSEMBLIES |
| | |
| | 11) 109.3.10* IMPACT OF CONSTRUCTION. |
| | ALL CONSTRUCTION ACTIVITY REGULATED BY |
| | THIS CODE SHALL BE PERMORMED IN A MANNER |
| | SO AS NOT TO ADVERSELY IMPACT THE |
| | CONDITION OF ADJACENT PROPERTY, UNLESS |
| | SUCH ACTIVITY IS PERMITTED TO AFFECT |
| | SAID PROPERTY PURSUANT TO A CONSENT BY |
| | THE APPLICABLE PROPERTY OWNER, UNDER |
| | TERMS & CONDITIONS AGREEABLE TO THE |
| | APPLICABLE PROPERTY OWNER.THIS INCLUDES |
| | BUT IS NOT LIMITED TO THE CONTROL OF |
| | DUST, NOISE, WATER OR DRAINAGE RUN-OFF, |
| | DEBRIS, AND THE STORAGE OF CONSTRUCTION |
| | MATERIALS. NEW CONSTRUCTION ACTIVITY |
| | SHALL NOT ADVERSELY IMPACT HISTORIC |
| | SURFACE WATER DRAINAGE FLOWS SERVING |
| | ADJACENT PROPERTIES, & MAY REQUIRE |
| | SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE |
| | POSITIVE PATTERNS OF THE AFFECTED SITES. |
| | ACCORDINGLY, DEVELOPERS, CONTRACTORS, |
| | AND OWNERS OF ALL NEW RESIDENTIAL |
| | DEVELOPMENT, INCLUDING ADDITIONS, POOLS, |
| | PATIOS, DRIVEWAYS, DECKS, OR SIMILAR |
| | ITEMS, ON EXISTING PROPERTIES RESULTING |
| | IN A DECREASE IN EXCESS OF 800SQ FT OF |
| | PERMEABLE LAND AREA ON ANY PARCELL SHALL |
| | AS A PERMIT CONDITION, PROVIDE A |
| | PROFESSIONALLY PREPARED DRAINAGE PLAN |
| | CLEARLY INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE |
| | IMPROVEMENT, A CERTIFICATE FROM A |
| | LICENSED ENGINEER SHALL BE SUBMITTED TO |
| | THE INSPECTOR IN ORDER TO RECEIVE |
| | APPROVAL OF THE FINAL INSPECTION. |
| | |
| | 12) 109.3.10.1 HURICANE PROTECTION. |
| | IT SHALL BE UNLAWFUL FOR ANY PERSON TO |
| | ALLOW CONSTRUCTION RELATED MATERIALS |
| | EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR |
| | OTHERWISE UNSECURED AT A CONSTRUCTION |
| | SITE FROM 24 HRS. AFTER A HURRICANE |
| | WATCH HAS BEEN ISSUED UNTIL THE |
| | HURRICANE WATCH OR WARNING HAS BEEN |
| | LIFTED. ALL SUCH CONSTRUCTION MATERIALS, |
| | EQUIPMENT AND DEBRIS SHALL BE EITHER |
| | REMOVED FROM THE CONSTRUCTION SITE OR |
| | SECURED IN SUCH A MANNER AS TO MINIMIZE |
| | THE DANGER OF SUCH CONSTRUCTION |
| | MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| | DAMAGE TO PERSONS OR PROPERTY FROM HIGH |
| | WINDS. |
| | ANY PERSONS WHO FAILS TO COMPLY TO |
| | REMOVE OR SECURE THE CONSTRUCTION |
| | MATERIALS EQUIPMENT AND DEBRIS WITHIN |
| | 24 HRS AFTER A HURRICANE WATCH HAS BEEN |
| | ISSUED SHALL BE SUBJECT TO A FINE NOT TO |
| | EXCEED $500.00. |
| | IN ADDITION TO THE ABOVE, A LICENSED |
| | CONTRACTOR WHO VIOLATES THIS SECTION |
| | SHALL BE SUBJECT TO DISCIPLINE PURSUANT |
| | TO SECTION 113 OF THIS CHAPTER. |
| | |
| | 13) PLANS DO NOT INDICATE WHAT TYPE OF |
| | PAPER BACK LATH WILL BE USED ON THE |
| | CEILING OR LENGTH OR TYPE OF NAIL. |
| | 2510 LATHING FOR CEMENT PLASTER (STUCCO) |
| | |
| | 2510.3 INSTALLATION. |
| | INSTALLATION OF THESE MATERIALS SHALL BE |
| | IN COMPLIANCE WITH ASTM C 926 AND ASTM C |
| | 1063. |
| | |
| | 14) PLANS DO NOT INDICATE COMPLIANCE |
| | WITH ATTIC VENTILATION, 1203.2. |
| | |
| | 15) PLANS INDICATE THAT THIS PAVILION IS |
| | LOCATED IN A ISLAND OF A PARKING LOT. |
| | PLEASE PROVIDE THE ACCESSIBLE ACCESS TO |
| | THE PAVILION, INDICATE AN ACCESSIBLE |
| | CROSS WALK, CURB CUTS AND DETECTABLE |
| | WARNING AT CROSSWALKS. |
| | |
| | 11-4.3.2 (2)AT LEAST ONE ACCESSIBLE |
| | ROUTE SHALL CONNECT ACCESSIBLE |
| | BUILDINGS, FACILITIES, ELEMENTS, AND |
| | SPACES THAT ARE ON THE SAME SITE. |
| | |
| | 11-4.3.8AT LEAST ONE ACCESSIBLE ROUTE |
| | SHALL CONNECT ACCESSIBLE BUILDINGS, |
| | FACILITIES, ELEMENTS, AND SPACES THAT |
| | ARE ON THE SAME SITE. |
| | |
| | 11-4.3.6 SURFACE TEXTURES. |
| | THE SURFACE OF AN ACCESSIBLE ROUTE SHALL |
| | COMPLY WITH SECTION 11-4.5 . |
| | |
| | 11-3.5 MARKED CROSSING. A CROSSWALK OR |
| | OTHER IDENTIFIED PATH INTENDED FOR |
| | PEDESTRIAN USE IN CROSSING A VEHICULAR |
| | WAY. |
| | |
| | 11-4.7.1 LOCATION. |
| | CURB RAMPS COMPLYING WITH SECTION 11-4.7 |
| | SHALL BE PROVIDED WHEREVER AN ACCESSIBLE |
| | ROUTE CROSSES A CURB. |
| | CURB RAMPS MUST BE LOCATED OUTSIDE OF |
| | DISABLED PARKING SPACES AND ACCESS |
| | AISLES. |
| | |
| | 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | BUILDING PLAN REVIEW |