| 2006-06-14 00:00:00 | DENIED |
| | |
| | 1) THE JOHNS MANVILLE EPDH SINGLE PLY |
| | ROOF SYSTEM OVER RECOVER DECKS PRODUCT |
| | APPROVAL SPECIFIES A MAXIMUM DESIGN |
| | PRESSURE OF -75 WITH INCREASE ALLOWED |
| | PER LIMITATION #9 ON PAGE 12. THIS |
| | DESIGN PRESSURE IS TOO LOW. SEE 2004 FBC |
| | TABLE 1609.6B FOR COMPONENT AND CLADDING |
| | WINDLOAD PRESSURES. |
| | |
| | 2) WHEN MULTIPLE ROOF ASSEMBLIES AND |
| | FASTENING OPTIONS ARE SPECIFIED IN THE |
| | PRODUCT APPROVAL PLEASE INDICATE THE ONE |
| | THAT WILL BE USED. |
| | |
| | 3) RECOVER OR ROOFOVERS REQUIRE THE |
| | EXISTING ROOF TO BE INSPECTED BY A |
| | BUILDING INSPECTOR BEFORE THE PERMIT CAN |
| | BE ISSUED. PLEASE INFORM THE PERMIT |
| | CLERK AT THE FRONT COUNTER WHEN |
| | SUBMITTING FOR PERMIT SO THAT THE |
| | APPLICATION CAN BE ROUTED TO THE |
| | APPROPRIATE PERSONNEL. |
| | |
| | 4)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. |
| | WWW.FLORIDABUILDING.ORG |
| | IF THE PRODUCT HAS STATE PRODUCT |
| | APPROVAL INDICATE THE STATE FL #. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |