Plan Review Notes
Plan Review Notes For Permit 06060788
Permit Number 06060788
Review Stop P
Sequence Number 1
Notes
Date Text
2006-06-23 00:00:00******DENIED******
 REFERENCE: FBC-2004 SEC. 424.2 OR
 FBC-2004 RESIDENTIAL SEC. R4101 SWIMMING
 POOLS:
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PUMBING PLAN REVIEW:
  
 1) PLEASE CORRELATE THE VENT SIZE ON
 PRINT. THE MAIN DRAIN DETAIL INDICATES
 1-1/2" AND THE PIPING SCHEMATIC
 INDICATES 1" PLEASE SEE CORRECTED
 DRAWING IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
 2) FBC-2004 SEC. 424.2.7.2, OR FBCR-2004
 SEC. R4101.7.2 PUMPS AND EQUIPMENT SHALL
 BE MOUNTED ON A SUBSTANTIAL BASE IN A
 MANNER THAT WILL ELIMINATE STRAIN ON
 PIPING.SLAB SHALL BE A NOMINAL 4"
 THICK. (DETAIL)
 3) PLEASE CHANGE SPECIFICATION NOTE #9
 ON THE GAS TO READ AS THE FOLLOWING.
 FBC-2004 SEC. 424.2.14, OR FBCR-2004
 SEC. R4101.15 GAS PIPING SHALL COMPLY
 WITH FBC FUEL GAS.SEPARATE PLANS AND
 PERMIT REQUIRED.
 4) FBC-2004 SEC. 424.2.14.4, OR
 FBCR-2004 SEC. R4101.14.4 CONNECTIONS,
 ALL WATER HEATING EQUIPMENT SHALL BE
 INSTALLED WITH FLANGES OR UNION
 CONNECTIONS ADJACENT TO THE HEATER.
 (ADD TO NOTES)
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  