| 2006-06-23 00:00:00 | ******DENIED****** |
| | REFERENCE: FBC-2004 SEC. 424.2 OR |
| | FBC-2004 RESIDENTIAL SEC. R4101 SWIMMING |
| | POOLS: |
| | |
| | THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR PUMBING PLAN REVIEW: |
| | |
| | 1) PLEASE CORRELATE THE VENT SIZE ON |
| | PRINT. THE MAIN DRAIN DETAIL INDICATES |
| | 1-1/2" AND THE PIPING SCHEMATIC |
| | INDICATES 1" PLEASE SEE CORRECTED |
| | DRAWING IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | 2) FBC-2004 SEC. 424.2.7.2, OR FBCR-2004 |
| | SEC. R4101.7.2 PUMPS AND EQUIPMENT SHALL |
| | BE MOUNTED ON A SUBSTANTIAL BASE IN A |
| | MANNER THAT WILL ELIMINATE STRAIN ON |
| | PIPING.SLAB SHALL BE A NOMINAL 4" |
| | THICK. (DETAIL) |
| | 3) PLEASE CHANGE SPECIFICATION NOTE #9 |
| | ON THE GAS TO READ AS THE FOLLOWING. |
| | FBC-2004 SEC. 424.2.14, OR FBCR-2004 |
| | SEC. R4101.15 GAS PIPING SHALL COMPLY |
| | WITH FBC FUEL GAS.SEPARATE PLANS AND |
| | PERMIT REQUIRED. |
| | 4) FBC-2004 SEC. 424.2.14.4, OR |
| | FBCR-2004 SEC. R4101.14.4 CONNECTIONS, |
| | ALL WATER HEATING EQUIPMENT SHALL BE |
| | INSTALLED WITH FLANGES OR UNION |
| | CONNECTIONS ADJACENT TO THE HEATER. |
| | (ADD TO NOTES) |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| | RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | |
| | END OF COMMENTS: |
| | |