Plan Review Notes
Plan Review Notes For Permit 06060788
Permit Number 06060788
Review Stop E
Sequence Number 1
Notes
Date Text
2006-06-22 00:00:00****** UNSAT ********
  
 1) NOTE: PLEASE COORELATE PLANS, AS
 PLUMB INDICATES A GAS HEATER AND THE
 ELECTRICAL INDICATES AN ELECTRICAL HEAT
 PUMP?
 215.5
 IF ELEC HEAT PUMP, SUBMIT LOAD
 CALCULATIONS FOR INCREASED LOADS WITH
 LOAD ON EXISTING SERVICE. PLEASE KNOW
 ALL CONTINUOUS LAODS AT 125%, THIS
 INCLUDE PUMPS AND HEATER.
 220, 215.3,230.42, 680.9 ETC
  
 2) NOTE: PLEASE SEE PLUMB INDICATES TWO
 PUMPS AND ONLY ONE SHOWN ON ELECTRICAL ,
 PLEASE ADJUST AND CORRELATE RISER.
 215.5
  
 3) NOTE: PLEASE SPECIFY IF PANEL SHOWN
 IS NEW OR EXSITING. IF NEW, PLEASE
 INDICATE THE OCP, FEEDERS ETC FOR NEW
 PANELS.; IF EXISTING, INDICATE OCP ,
 CONDUCTORS AND BRANCH CIRCUITS FOR NEW
 LAODS.
 215.5,240.4,310.16 ETC
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  