| 2006-06-22 00:00:00 | ****** UNSAT ******** | | | | | | 1) NOTE: PLEASE COORELATE PLANS, AS | | | PLUMB INDICATES A GAS HEATER AND THE | | | ELECTRICAL INDICATES AN ELECTRICAL HEAT | | | PUMP? | | | 215.5 | | | IF ELEC HEAT PUMP, SUBMIT LOAD | | | CALCULATIONS FOR INCREASED LOADS WITH | | | LOAD ON EXISTING SERVICE. PLEASE KNOW | | | ALL CONTINUOUS LAODS AT 125%, THIS | | | INCLUDE PUMPS AND HEATER. | | | 220, 215.3,230.42, 680.9 ETC | | | | | | 2) NOTE: PLEASE SEE PLUMB INDICATES TWO | | | PUMPS AND ONLY ONE SHOWN ON ELECTRICAL , | | | PLEASE ADJUST AND CORRELATE RISER. | | | 215.5 | | | | | | 3) NOTE: PLEASE SPECIFY IF PANEL SHOWN | | | IS NEW OR EXSITING. IF NEW, PLEASE | | | INDICATE THE OCP, FEEDERS ETC FOR NEW | | | PANELS.; IF EXISTING, INDICATE OCP , | | | CONDUCTORS AND BRANCH CIRCUITS FOR NEW | | | LAODS. | | | 215.5,240.4,310.16 ETC | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | |
|