Plan Review Notes For Permit 06060788
Permit Number 06060788
Review Stop B
Sequence Number 1
Notes
Date Text
2006-07-03 00:00:00 
 1) THE ZONING ISSUES SHALL BE ADDRESSED
 BEFORE THE APPLICATION CAN BE APPROVED
 BY THE STRUCTUAL REVIEWER.
  
 2) NOTE: THE SLAB FOR THE EQUIPEMENT
 TIE-DOWN SHALL BE SOLID CONCRETE.
 ?1820.3. CONCRETE FLOOR SLABS PLACED
 DIRECTLY ON THE SUPPORTING SOIL
 SHALL BE A MINIMUM OF 4 INCHES IN
 THICKNESS, REINFORCED WITH NOT LESS THAN
 0.028 SQUARE INCHES OF REINFORCING PER
 LINEAR FOOT OF SLAB IN EACH
 DIRECTION.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER