Plan Review Notes
Plan Review Notes For Permit 06060787
Permit Number 06060787
Review Stop P
Sequence Number 1
Notes
Date Text
2006-06-23 00:00:00******DENIED******
 REFERENCE: FBC-2004 SEC. 424.2 OR
 FBC-2004 RESIDENTIAL SEC. R4101 SWIMMING
 POOLS:
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLUMBING PLAN REVIEW:
  
 1) FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (MANUFACTURE
 SHEETS REQUIRED, PLEASE SUBMIT)
 2) FBC-2004 SEC. 424.2.14.2, OR
 FBCR-2004 SEC. R4101.14.2 WATER
 RETENTION, PROVIDE A POSITIVE MEANS OF
 RETAINING WATER IN THE HEATER WHEN PUMP
 IS SHUT OFF.(MANUFACTURE SHEETS
 REQUIRED, PLEASE SUBMIT)
  
 END OF COMMENTS:
  