Plan Review Notes
Plan Review Notes For Permit 06060787
Permit Number 06060787
Review Stop E
Sequence Number 1
Notes
Date Text
2006-06-22 00:00:00******** UNSAT *********
  
  
 1) NOTE: PLEASE CORRELATE PLANS FOR ALL
 EQUIPMENT, CONDCUCTORS SIZES ETC.
 215.5
 PLEASE SEE PLANS INDICATE AN ELECTRIC
 HEAT PUMP, YET RISER SHOWS ONLY #12'S?
 PLEASE SEE POOL PUMP INDICATES 3-8'S??
 PLEASE KNOW THAT 3-#8'S WILL NOT CONNECT
 INSIDE A 1 1/2 HP PUMP.
  
 2) NOTE: PLEASE SEE DIAGRAM SHOWS A NEW
 POOL PANEL YET NO OCP IS SHOWN FROM
 EXISTING LOCATION ETC.
 215.5
  
 3) NOTE: PLEASE SEE MORE THAN ONE
 LOCATION WHICH INDICATES 3-#8'S IN A
 1/2" CONDUIT? PLEASE SEE MISSING
 EQUIPMENT GROUNDING CONDUCTORS IN MORE
 THAN ONE OF THESE CONDUITS. PLEASE SEE
 680, 250.110,250.122 ETC FOR GROUNDING.
 PLEASE SEE TABLES 9 FOR MAX CONDUIT
 FILL.
  
 4) NOTE: PLEASE SUBMIT COMPLETE LOAD
 CALCULATIONS FOR ALL NEW EQUIPMENT BEING
 ADDED TO EXSITIGN SERVICE. PLEASE BE
 SURE ALL CONTINUOUS LOADS ARE SHOWNAT
 125%. 215.3,230.42,680.9
 PLEASE ALSO INDICATE SIZE OF EXISTING
 SERVICE.
 215.5,220.31B
  
 5) NOTE: PLEASE SUBMIT MANUFACTURES
 SPECS/ CUT SHEETS FOR NEW PROPOSED HEAT
 PUMP. ALL MUST INDICATE THE LISTING FROM
 A NRTL.
 110.3
  
 ** PLEASE KNOW, ALL OVERHEAD POWER LINES
 SHALL MEET 680.8
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  