2006-11-03 07:27:36 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1}PROVIDE A RISER DIAGRAM FOR THE PROPOSED
 SERVICE.THE ONE SUBMITTED WAS EXISTING.
  
 2} PROVIDE PANEL SCHEDULES FOR ALL PANELS PER
 106.3.5.4(8) FBC AS AMMENDED.
  
 3}PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT.
  
 4} THE RISER INDICATES PANEL "A" FEEDING PANEL "B"
 USING 3 #1 CONDUCTORS, INDICATE THE OCP IN PANEL "A"
 PANEL SCHEDULE.
  
 5} PROVIDE AN EQUIPMENT GROUNDING CONDUCTOR WITH THE
 FEED FOR PANE L"B" PER 250.122.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.