Plan Review Notes
Plan Review Notes For Permit 06060758
Permit Number 06060758
Review Stop E
Sequence Number 1
Notes
Date Text
2006-08-11 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SEE NOTE #1 INCORRECTLY
 IDENTIFIES THE 2005 FBC AS THE DESIGN
 DOCUMENT. THE STSTE OF FLORIDA PER 553
 FS HAS ADOPTED THE 2004 FBC AND ALL
 REFERENCED MATERIAL.
  
 2} PLEASE PROVIDE A PANEL SCHEDULE SO
 THAT BRANCH/FEEDER CIRCUIT CONDUCTOR AND
 OVER CURRENT PROTECTION COMPLIANCE MAY
 BE REVIEWED PER 106.3.5.4 FBC AS
 AMENDED.
  
 3} A GROUNDING ELECTRODE CONDUCTOR IS
 REQUIRED AT THE SEPARATE STRUCTURE PER
 250.32, SIZED PER 250.66. PROVIDE A
 RISER DIAGRAM INDICATING COMPLIANCE.
  
 4} PLEASE GIVE SPECIFICATIONS FOR THE
 PANELS SHOW, AMPERAGE/VOLTAGE RATING,
 FEEDER SIZE AND DISCONNECTING MEANS PER
 225.31.
  
 5} THE CALCULATION GIVEN IS INCOMPLETE.
 SEE 220. 30 OR 220.31. FOR INSTRUCTIONS.
 INDICATE WHICH ARTICLE IS USED.
  
 6}PROVIDE A LOAD CALCULATION FOR THE
 COMPLETE SERVICE, INDICATE THE EXISTING
 SERVICE SIZE, SHOWN EXISTING AND NEW
 SEPARATE, THEN TOGETHER.
  
 7}} PROVIDE A RISER DIAGRAM WITH
 CONDUCTOR AND CONDUIT SIZE AND TYPE,
 GROUNDING DETAILS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  