| 2006-08-11 00:00:00 | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PLEASE SEE NOTE #1 INCORRECTLY |
| | IDENTIFIES THE 2005 FBC AS THE DESIGN |
| | DOCUMENT. THE STSTE OF FLORIDA PER 553 |
| | FS HAS ADOPTED THE 2004 FBC AND ALL |
| | REFERENCED MATERIAL. |
| | |
| | 2} PLEASE PROVIDE A PANEL SCHEDULE SO |
| | THAT BRANCH/FEEDER CIRCUIT CONDUCTOR AND |
| | OVER CURRENT PROTECTION COMPLIANCE MAY |
| | BE REVIEWED PER 106.3.5.4 FBC AS |
| | AMENDED. |
| | |
| | 3} A GROUNDING ELECTRODE CONDUCTOR IS |
| | REQUIRED AT THE SEPARATE STRUCTURE PER |
| | 250.32, SIZED PER 250.66. PROVIDE A |
| | RISER DIAGRAM INDICATING COMPLIANCE. |
| | |
| | 4} PLEASE GIVE SPECIFICATIONS FOR THE |
| | PANELS SHOW, AMPERAGE/VOLTAGE RATING, |
| | FEEDER SIZE AND DISCONNECTING MEANS PER |
| | 225.31. |
| | |
| | 5} THE CALCULATION GIVEN IS INCOMPLETE. |
| | SEE 220. 30 OR 220.31. FOR INSTRUCTIONS. |
| | INDICATE WHICH ARTICLE IS USED. |
| | |
| | 6}PROVIDE A LOAD CALCULATION FOR THE |
| | COMPLETE SERVICE, INDICATE THE EXISTING |
| | SERVICE SIZE, SHOWN EXISTING AND NEW |
| | SEPARATE, THEN TOGETHER. |
| | |
| | 7}} PROVIDE A RISER DIAGRAM WITH |
| | CONDUCTOR AND CONDUIT SIZE AND TYPE, |
| | GROUNDING DETAILS. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |