| Date |
Text |
| 2006-11-20 09:02:28 | *** UNSAT 2ND REVIEW *** |
| | |
| | |
| | *** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH IS |
| | STILL IN NEED OF ADDRESSING. PLEASE ALSO WEE NOTES |
| | WHICH ARE NEW BASED ON REVISED ITEMS NOW SHOWN ON |
| | PLANS. |
| | |
| | ** PLEASE SEE NOTES BELOW ARE TAKEN DIRECTLY FROM |
| | PREVIOUS REVIEW AND MARKED WITH AN OK! , NO! (WITH |
| | FURTHER EXPLANATION) OR SOME MAY BE LABELED WITH OK/NO |
| | AS PART OF THE COMMENT MAY HAVE BEEN ADDRESSED ONLY. |
| | |
| | |
| | 1) NOTE: OK. |
| | |
| | 2) NOTE: OK. |
| | |
| | 3) NOTE: OK. |
| | |
| | 4) NOTE: OK. |
| | |
| | 5) NOTE:NO, PLEASE SEE THE COMMENT AS PREVIOUSLY |
| | NOTED WAS TO OBTAIN CORRECT LOCATION TO BE COORDINATED |
| | WITH THE FIRE MARSHAL'S OFFICE AND SHALL BE SHOWN AND |
| | NOTED ON THE PLANS THIS WAY. THE PLANS RESPONSE AND |
| | "KEY NOTE" READS TO BE LOCATED WITH THE OWNER. THIS IS |
| | THE DECISION OF THE FIRE MARSHAL'S OFFICE AND THE CODE |
| | ONLY. PLEASE ALSO SEE CODE SECTION AS PREVIOUSLY GIVEN. |
| | FOR LOCATION REQUIREMENTS |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW # 1 ** |
| | PLEASE SEE GEN ANNUCIATOR PANEL SHALL BE LOCATED IN THE |
| | FIRE COMMAND ROOM, OR LOCATION OF FACP, NEAREST POINT |
| | DESIGNATED BY THE FIRE MARSHAL'S OFFICE. |
| | NFPA-101 CHAPTER 11.8.5. |
| | |
| | 6) NOTE: OK. RESPONSE LETTER MENTIONS THERE IS A DIESEL |
| | DRIVEN FIRE PUMP. |
| | |
| | |
| | 7) NOTE: OK/ NO, |
| | PLEASE SEE SPECIFICATIONS FROM THE MANUFACTURE STILL |
| | INDICATE AS 706 GALLONS. RESPONSE LETTER MENTIONS THAT |
| | THE TANK WILL BE BAFFLED, YET THE SPECIFICATIONS FROM |
| | THE MANUFACTURE NEED TO INDICATE THIS AT THIS TIME. |
| | PLEASE SEE REVIEW COMMENTS FROM OTHER TRADES. |
| | |
| | |
| | |
| | |
| | 8) NOTE: OK, HOWEVER SEE NEW NOTES. |
| | |
| | |
| | 9) NOTE:NO, PLEASE SEE PREVIOUS NOTE, AS SHOWN ON |
| | PLANS, 4-POLE TRANSFER SWITCHES WILL BE REQUIRED. THIS |
| | IS BASED ON THE RISER AS SHOWN. THE GENERATOR IS BEING |
| | SHOWN AS SEPARETLY DERIVED, EVEN THOUGH NOTE MENTIONS |
| | IT WILL NOT BE. |
| | PLEASE SEE RISER. |
| | |
| | ** PREVIOUS REVIEW NOTE FROM REVIEW #1 ** |
| | PLEASE SEE NOTES MENTIONS THAT THE GEN WILL "NOT" BE A |
| | "SEPARATELY |
| | DERIVED SYSTEM" YET, GENERATOR SEEMS TO |
| | BE SHOWN WITH A BOND FROM THE GEN FRAME AND GROUND BAR |
| | TO THE GEN WINDINGS? |
| | PLEASE KNOW, IF THIS OCCURS, THEN THIS "IS" A SDS AND |
| | SHALL THEN CONTAIN A |
| | 4-POLE ATS'S, GE SYSTEM AND NOTED AS SO. |
| | PLEASE VERIFY AND ADJUST PLANS AS NEEDED. |
| | |
| | 10) NOTE: NO, PLEASE SEE THIS WAS SUBMITTED; HOWEVER |
| | PLEASE SEE THE SHEETS IN FACT CONTAIN RAISED SEALS OVER |
| | A "PHOTO-COPIED" SIGNATURE FROM THE ENGINEER OF RECORD. |
| | ( MR. ALBERT KWAN) PLEASE SEE FLORIDA STATUTES 471.025, |
| | AND FLORIDA ADMINISTRATIVE CODE 61G15-23.002. PLEASE |
| | KNOW THIS IS REVIEW WHETHER OR NOT COMMENT IS MADE BY |
| | BUILDING REVIEW. |
| | PLEASE ALSO SEE SHEET MENTIONS TO BE 6INCHES ABOVE |
| | FLOOR ELEVATION HOWEVER, EQUIPMENT SHALL BE 6 INCHES |
| | ABOVE THE BFE BASED ON THE 100 YR YEAR STORM SURGES |
| | LEVELS OR SURGE LEVELS BASED ON A CAT 4 STORM. PLEASE |
| | SEE SLOSH CHARTS ETC. |
| | PLEASE SEE SECTIONS GIVEN IN PREVIOUS REVIEW NOTE. |
| | |
| | ** PREVIOUS REVIEW NOTE FROM REVIEW #1 ** |
| | PLEASE BUILDING REVIEW COMMENTS WITH RESPECT TO THE |
| | GEN SLAB DETAIL. PLEASE SEE NO DETAIL, CONNECTIONS, |
| | ELEVATIONS WERE SUBMITTED. |
| | PLEASE ALSO SEE NOTE MENTIONS THE GEN @ OR ABOVE BFE. |
| | PLEASE KNOW, THE GEN/ ASSOCIATED EQUIPMENT SHALL BE 6" |
| | ABOVE THE BFE. |
| | PLEASE SEE NFPA-110 CHAPTER 7, 7.2, 7.3, |
| | 7.4, 7.9 ETC. |
| | ** PLEASE KNOW, DUE TO THE SIZE, WEIGHT, EPSS |
| | REQUIREMENTS ETC,THE SLAB WILL BE REQUIRED TO BE |
| | SIGNED, DATED AND SEALED BY AN ENGINEER. |
| | FS 471.003 |
| | |
| | 11) NOTE:NO, SAME NOTE. |
| | |
| | ** PREVIOUS REVIEW NOTE FROM REVIEW #1 ** |
| | PLEASE BE SURE THE ENGINEER OF RECORD SIGNS PLANS WITH |
| | HIS LEGAL/EASILY RECOGNIZABLE SIGNATURE KNOWN TO THIS |
| | OFFICE AND ON RECORD IN THIS OFFICE. |
| | FS 471.025, FAC 61G15-23.002 |
| | |
| | |
| | **** NEW NOTES FROM THE 2ND REVIEW *** |
| | |
| | 12) NOTE: PLEASE SUBMIT THE MANUFACTURE |
| | SPECIFICATION/CUT SHEETS ON THE WP HOUSING FOR THE |
| | GENERATOR. |
| | FBC 106.1.2, |
| | 110.3,90.7 |
| | |
| | 13) NOTE: PLEASE BE SURE EITHER PLANS OR MANUFACTURE |
| | SPECIFICATIONS INDICATE THE FUEL CONSUMPTION BASED ON |
| | DIESEL ONLY. |
| | SPECS APPEAR TO SHOW AS BI-FUEL ONLY. |
| | |
| | 14) NOTE: PLEASE SEE RESPONSE LETTER MENTIONS SHEETS |
| | EQ.1, IS THIS NOT E0.1? THIS ONLY APPEARS TO BE A |
| | MISPRINT. |
| | PLEASE EXPLAIN RATIONAL ON THE SIZING OF THE BREAKERS |
| | FROM THE GENERATOR. PLEASE SEE THE EMDP HAS A LOAD OF |
| | 238A'S +/- WITH A 300A BREAKER FEEDING THIS 600A PANEL |
| | BOARD. WHEREAS THE PANEL "HEQ" WHICH IS ONLY RATED |
| | 400A'S AND HAS ONLYA LOAD OF 105A'S +/- , YET HAS A |
| | 350A BREAKER AT THE GENERATOR FOR OVER CURRENT |
| | PROTECTION. |
| | THIS IS UNCLEAR WHY THE EQUIPMENT WITH LOAD WHICH IS |
| | SUBSTANTIALLY MORE CONTAINS A LOWER OVER CURRENT |
| | PROTECTION. |
| | PLEASE EXPLAIN AND CORRELATE. |
| | FBC 106.1.2 ADMIN SECT. |
| | |
| | 15) NOTE: PLEASE SEE FEEDER SCHEDULE ON RISER AND THAT |
| | ON MDP2, PLEASE CORRELATE. PLEASE ALSO SEE FEEDER |
| | SCHEDULE. |
| | |
| | 16) NOTE: PLEASE SEE RISER SHOWS A TRANSFORMER T-8 |
| | BEING FED FROM HEQ, YET HEQ WITH THE CIRCUITS AS SHOWN |
| | ON RISER INDICATE THESE AS ?SPARE? ON SCHEDULE??? |
| | PLEASE CORRELATE CIRCUITING AS SHOWN FROM RISER TO |
| | PANEL SCHEDULE. |
| | FBC 106.1.2 ADMIN SECTION. |
| | |
| | 17) NOTE: PLEASE HIGH-LIGHT THE SPECIFIC TRANSFER |
| | SWITCH BEING USED ON THE MANUFACTURE SPECS/CUT SHEETS |
| | SUBMITTED. THERE IS A "SUGGESTED SPECIFICATION" BOOKLET |
| | SUBMITTED, HOWEVER PLEASE INDICATE ON SPECS. |
| | 110.3,90.7. |
| | FBC 106.1.2 |
| | |
| | |
| | |
| | |
| | ** ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| | **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF |
| | THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE |
| | DO NOT HESITATEIN CONTACTING THIS REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |