| Plan Review Notes For Permit 06060723 |
| Permit Number |
06060723 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-08-21 00:00:00 | DENIED: | | | 1.PLEASE PROVIDE DISTANCES/CLEARANCES | | | TO THE FOLLOWING; PROPERTY LINES, | | | BUILDINGS, FRESH AIR INTAKES, WINDOWS, | | | DOORS, LOUVERS, ETC.SHOW COMPLIANCE | | | WITH 2004 FMC 401.5. | | | | | | 2.INDICATE IF PROTECTION FROM DAMAGE | | | IS REQUIRED IN ACCORDANCE WITH 2004 FMC | | | 303.4. | | | | | | 3.PROVIDE DETAIL INFORMATION ON THE | | | ANCHORING OF THE GENERATOR. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719 OR | | | E-MAIL [email protected]. |
|