| 2006-08-18 00:00:00 | ***DENIED*** | | | | | | 1) PLEASE SEE OTHER REVIEW COMMENTS | | | REGARDING ADDRESSING AND MAKE | | | CORRECTION. THE ADDRESS SHOULD REFLECT | | | 1001 OKEECHOBEE BLVD. | | | | | | 2) NFPA 101, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 3) PLEASE CLEARLY IDENTIFY LOCATION OF | | | GENERATOR AND FUEL TANK WITH RELATION TO | | | BUILDING OPENINGS AND ILLUSTRATE | | | DISTANCES. PLEASE SUBMIT SITE PLAN FOR | | | REVIEW. | | | | | | 4) WORK TO COMPLY WITH NFPA 110, 2002 | | | EDITION. | | | | | | 5) DEPENDANT UPON LOCATION OF EQUIPMENT, | | | SAFEGUARDS AGAINST MECHANICAL DAMAGE MAY | | | BE REQUIRED AND SHALL BE ILLUSTRATED. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|