Text |
| 2006-06-30 00:00:00 | ********* UNSAT ********* |
| | |
| | 1) NOTE: PLEASE SEE ADDRESSING REVIEW |
| | AND COMMENTS AS THE CORRECT ADDRESS FOR |
| | THE MARRIOT IS 1001 OKEECHOBEE BLVD. |
| | THIS ADDRESS WAS CHANGED A COUPLE OF |
| | YEARS AGO. |
| | PLEASE ADJUST ALL PLANS/TITLE BLOCKS ARE |
| | REQUIRED FAC 61G15-23.002/61G1-16.004 |
| | |
| | 2) NOTE: PLEASE CLARIFY THE KW RATING OF |
| | THE GEN AS ONE SHEET IN THE |
| | SUBMITTAL/SPEC PACKAGE CONTAINS 400KW? |
| | |
| | 3) NOTE: PLEASE BE SURE TO PROVIDE ALL MANUFACTURES |
| | CUT/SPEC SHEETS FOR GEN AND |
| | ATS. APPEARS TO BE MISSING COVER SHEETS |
| | ETC. |
| | FBC ADMIN SECT 106.1.2 |
| | |
| | 4) NOTE: PLEASE SEE THAT PLANS REFLECT |
| | ALL CURRENT CODES IN AFFECT. |
| | NFPA-70 2002, NFPA-101 2003, NFPA-110 |
| | 2002. |
| | |
| | 5) NOTE: PLEASE SEE GEN ANNUCIATOR PANEL |
| | SHALL BE LOCATED IN THE FIRE COMMAND |
| | ROOM, OR LOCATION OF FACP, NEAREST POINT DESIGNATED BY |
| | THE FIRE MARSHAL'S OFFICE. |
| | NFPA-101 CHAPTER 11.8.5. |
| | |
| | 6) NOTE: PLEASE CLARIFY IF THE FIRE PUMP |
| | IS FED FROM THIS GEN. ?? |
| | IF SO, PLEASE KNOW, THERE MUST BE A MIN |
| | OF 8HRS "ON-SITE" FUEL FOR 100% OF THE |
| | FULL LOAD RATING OF THE FIRE PUMP AND |
| | OTHER ASSOCIATED EM EQUIPMENT.2003 |
| | NFPA-20 9.6.2.2 |
| | PLEASE ALSO PROVIDE GPH WITHOUT THE TIE |
| | IN OF THE NAT GAS LINE AND WITH THE TIE |
| | IN OF THE NAT GAS LIN. |
| | |
| | |
| | 7) NOTE: PLEASE SEE FIRE REVIEW AND |
| | MECHANICAL REVIEW COMMENTS WITH RESPECT |
| | TO FUEL PIPING/ TANK SIZE AND STORAGE. |
| | 7.9.12LISTED GENERATOR SUB-BASE |
| | SECONDARY CONTAINMENT FUEL TANKS OF 2498 |
| | L (660 GAL) CAPACITY AND BELOW SHALL BE |
| | PERMITTED TO BE INSTALLED OUTDOORS OR |
| | INDOORS WITHOUT DIKING OR REMOTE |
| | IMPOUNDING. |
| | 7.9.12.1A MINIMUM CLEARANCE OF 0.9 M |
| | (36 IN.) SHALL BE MAINTAINED ON ALL |
| | SIDES. |
| | 7.9.3.1GALVANIZED FUEL LINES SHALL NOT |
| | BE USED. |
| | ** |
| | PLEASE SEE TANK SIZE IS BEING INDICATED |
| | AS 706 GALS. |
| | |
| | |
| | 8) NOTE: PLEASE SEE ATS-LS IS BEING FROM |
| | A 400A OCP AND EQUIPMENT IS RATED FOR |
| | 300A'S AND FEED FROM GEN IS 250A'S?? |
| | PLEASE CORRELATE. |
| | 215.5 |
| | |
| | 9) NOTE: PLEASE SEE NOTES MENTIONS THAT |
| | THE GEN WILL "NOT" BE A "SEPARATELY |
| | DERIVED SYSTEM" YET, GENERATOTR SEEMS TO |
| | BE SHOWN WITH A BOND FRON THE GEN FRAME |
| | AND GRND BAR TO THE GEN WINDINGS? |
| | PLEASE KNOW, IF THIS OCCURS, THEN THIS |
| | "IS" A SDS AND SHALL THEN CONTAIN A |
| | 4-POLE ATS'S, GE SYSTEM ANDNOTED AS |
| | SO. |
| | PLEASE VERIFY AND ADJUST PLANS AS |
| | NEEDED. |
| | |
| | 10) NOTE: PLEASE BUILDING REVIEW |
| | COMMENTS WITH RESPECT TO THE GEN SLAB |
| | DETAIL. PLEASE SEE NO DETAIL, |
| | CONNECTIONS, ELEVATIONS WERE SUBMITTED. |
| | PLEASE ALSO SEE NOTE MENTIONS THE GEN @ |
| | OR ABOVE BFE. PLEASE KNOW, THE GEN/ |
| | ASSOCIATED EQUIPMENT SHALL BE 6" ABOVE |
| | THE BFE. |
| | PLEASE SEE NFPA-110 CHAPTER 7, 7.2,7.3, |
| | 7.4,7.9 ETC. |
| | ** PLEASE KNOW, DUE TO THE SIZE, WEIGHT, |
| | EPSS REQUIREMNTS ETC,THE SLAB WILL BE |
| | REQUIRED TO BE SIGNED, DATED AND SEALED |
| | BY AN ENGINEER. |
| | FS 471.003 |
| | |
| | 11) NOTE: PLEASE BE SURE THE ENGINEER OF |
| | RECORD SIGNS PLANS WITH HIS LEGAL/EASILY RECOGNIZABLE |
| | SIGNATURE KNOWN TO THIS |
| | OFFICE AND ON RECORD IN THIS OFFICE. |
| | FS 471.025, FAC 61G15-23.002 |
| | |
| | ** PLEASE BE SURE TO SEE ANY OTHER |
| | COMMENTS FROM OTHER TRADES WHICH MAY |
| | AFFECT ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |