| 2006-08-08 00:00:00 | | | | | | | DENIED | | | | | | 1) PLEASE SEE THAT THERE ARE MANY | | | DISCREPANCIES ON 2/2 OF DRAWINGS BETWEEN | | | THE FRAMING PLAN AND SECTIONS C-C AND | | | D-D | | | SECTION C-C SHOWS PURLINS D-D OUT | | | LOOKERS, BEAM HT ON C-C AND D-D DO NOT | | | MAKE SENSE SEE THAT RAFTERS SIT ON BEAM | | | AT 7'-3" C-C AND TOP OF RAKE BEAM D-D IS | | | ALSO 7'-3" AT THE EAVE. MEANWHILE | | | FRAMING PLAN STATES 6'-5" BEAM ELEV. 2 | | | DIFFERINGSTIRRUP DETAILS ON D-D, C-C | | | SHOWS SPAN OF 18'-3" WHILE D-D HAS THAT | | | FOR HALF THE SPAN. PLEASE BE AWARE BEAM | | | IS 14 INCHES AND RAFTERS ARE 2X12 | | | (11 1/4") | | | BEAM SCHEDULE HAS BEAMS 8X14 C-C AND D-D | | | STATES 12X14 | | | ALSO SEE ON PAGE 1/2 A-A AND S-S HAVE | | | DIFFERENT ELEVATIONS | | | | | | 2) HOW DOES NEW ROOF FRAMING ATTACH TO | | | EXISTING STRUCTURE | | | | | | 3) NORTH ELEVATION SHOWS FRENCH DOORS AS | | | EXISTING BUT EXISTING FLOOR PLAN AND NEW | | | FLOOR PLAN SHOW NEW DOORS AND SIDELITES | | | PLEASE CLARIFY IF THEY ARE NEW PRODUCT | | | APPROVALS WILL BE REQUIRED | | | *****PLEASE CLARIFY ALL OF ABOVE****** | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 | | | | | | | | | | | | | | | | | | |
|