Notes
Date Text
2006-08-08 00:00:00 
  
 DENIED
  
 1) PLEASE SEE THAT THERE ARE MANY
 DISCREPANCIES ON 2/2 OF DRAWINGS BETWEEN
 THE FRAMING PLAN AND SECTIONS C-C AND
 D-D
 SECTION C-C SHOWS PURLINS D-D OUT
 LOOKERS, BEAM HT ON C-C AND D-D DO NOT
 MAKE SENSE SEE THAT RAFTERS SIT ON BEAM
 AT 7'-3" C-C AND TOP OF RAKE BEAM D-D IS
 ALSO 7'-3" AT THE EAVE. MEANWHILE
 FRAMING PLAN STATES 6'-5" BEAM ELEV. 2
 DIFFERINGSTIRRUP DETAILS ON D-D, C-C
 SHOWS SPAN OF 18'-3" WHILE D-D HAS THAT
 FOR HALF THE SPAN. PLEASE BE AWARE BEAM
 IS 14 INCHES AND RAFTERS ARE 2X12
 (11 1/4")
 BEAM SCHEDULE HAS BEAMS 8X14 C-C AND D-D
 STATES 12X14
 ALSO SEE ON PAGE 1/2 A-A AND S-S HAVE
 DIFFERENT ELEVATIONS
  
 2) HOW DOES NEW ROOF FRAMING ATTACH TO
 EXISTING STRUCTURE
  
 3) NORTH ELEVATION SHOWS FRENCH DOORS AS
 EXISTING BUT EXISTING FLOOR PLAN AND NEW
 FLOOR PLAN SHOW NEW DOORS AND SIDELITES
 PLEASE CLARIFY IF THEY ARE NEW PRODUCT
 APPROVALS WILL BE REQUIRED
 *****PLEASE CLARIFY ALL OF ABOVE******
  