| 2006-08-17 00:00:00 | DENIED: |
| | 1.PLAN SHEET M0.1 VENTILATION |
| | COMPLIANCE STATEMENT, NOTE 1 INDICATES |
| | ASHRAE STANDARD 62-2004.THE ASHRAE |
| | STANDARD REFERENCED IN THE CURRENT CODE |
| | IS 62-2001.PLEASE CORRECT. |
| | |
| | 2.PLAN SHEET M2.1 DETAIL 4 OF THE ROOF |
| | MOUNTED CURB.PER 2004 FBC 1509.7 ROOF |
| | MOUNTED MECHANICAL UNITS SHALL BE |
| | MOUNTED ON CURBS RAISED A MINIMUM OF 8" |
| | ABOVE THE ROOF SURFACE. |
| | |
| | 3.ADDITIONAL PERMITS REQUIRED FOR |
| | HOODS, FIRE SUPPRESSION, AND WALK IN |
| | COOLERS.PLEASE PROVIDE PLANS AND |
| | MANUFACTURER'S SUBMITTAL DATA WITH |
| | PERMIT APPLICATION. |
| | |
| | PLANS FOR THE HOOD SHOULD INDICATE THE |
| | FOLLOWING: |
| | - INDICATE GAUGE OF THE GREASE DUCT AS |
| | WELL AS THE DUCT TO THE HEAT HOOD PER |
| | NFPA 96-01 CHAPTER 7 & 2004 FMC |
| | 506.3.1.2. |
| | |
| | - ROOFTOP TERMINATION OF THE GREASE |
| | DUCT, SHOW COMPLIANCE WITH NFPA 96-2001 |
| | SUB-CHAPTER 7.8.2.1, ITEMS 1 THROUGH 8. |
| | |
| | - PROVIDE AIR VELOCITY THROUGH DUCT PER |
| | 2004 FMC 506.3.4. |
| | |
| | - PROVIDE A DETAIL FOR HANGING THE HOOD. |
| | |
| | - PROVIDE PLANS FOR THE FIRE SUPPRESSION |
| | IN ACCORDANCE WITH NFPA 96-01.PLEASE |
| | NOTE, ADDITIONAL PERMIT REQUIRED. |
| | |