2006-08-17 00:00:00DENIED:
 1.PLAN SHEET M0.1 VENTILATION
 COMPLIANCE STATEMENT, NOTE 1 INDICATES
 ASHRAE STANDARD 62-2004.THE ASHRAE
 STANDARD REFERENCED IN THE CURRENT CODE
 IS 62-2001.PLEASE CORRECT.
  
 2.PLAN SHEET M2.1 DETAIL 4 OF THE ROOF
 MOUNTED CURB.PER 2004 FBC 1509.7 ROOF
 MOUNTED MECHANICAL UNITS SHALL BE
 MOUNTED ON CURBS RAISED A MINIMUM OF 8"
 ABOVE THE ROOF SURFACE.
  
 3.ADDITIONAL PERMITS REQUIRED FOR
 HOODS, FIRE SUPPRESSION, AND WALK IN
 COOLERS.PLEASE PROVIDE PLANS AND
 MANUFACTURER'S SUBMITTAL DATA WITH
 PERMIT APPLICATION.
  
 PLANS FOR THE HOOD SHOULD INDICATE THE
 FOLLOWING:
 - INDICATE GAUGE OF THE GREASE DUCT AS
 WELL AS THE DUCT TO THE HEAT HOOD PER
 NFPA 96-01 CHAPTER 7 & 2004 FMC
 506.3.1.2.
  
 - ROOFTOP TERMINATION OF THE GREASE
 DUCT, SHOW COMPLIANCE WITH NFPA 96-2001
 SUB-CHAPTER 7.8.2.1, ITEMS 1 THROUGH 8.
  
 - PROVIDE AIR VELOCITY THROUGH DUCT PER
 2004 FMC 506.3.4.
  
 - PROVIDE A DETAIL FOR HANGING THE HOOD.
  
 - PROVIDE PLANS FOR THE FIRE SUPPRESSION
 IN ACCORDANCE WITH NFPA 96-01.PLEASE
 NOTE, ADDITIONAL PERMIT REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.